403.1.1 Pipe Size and Pressure Limitations
Go To Full Code Chapter
- All requirements for installation of gas distribution piping shall be in accordance with Chapter 4. Gas distribution piping with operating pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G.
- Gas distribution piping operating at a pressure of over 1/2 psig (3.5 kPa gauge) shall be welded.
Exception: Manufactured and listed gas trains provided with the appliance may be threaded.
- All welding of gas distribution piping shall be subject to radiography or special inspection as set forth in Section 406.
- Threaded piping may be used up to 4 inches (101.6 mm) in diameter at pressure no greater than 1/2 psig (3.5 kPa gauge). All piping greater than 4 inches in diameter shall be welded, regardless of operating pressure.
- All welded piping 21/2 inches (63.5 mm) or greater in diameter shall be butt-welded, and welded piping less than 21/2 inches (63.5 mm) in diameter may be socket-welded or butt-welded.
Upcodes Diagrams
Related Code Sections
403.1.1 Gas Piping Installations, Pipe Size and Pressure Limitations
1. All requirements for installation of gas distribution piping with operating pressures at 1/2 psig (3.5 kPa gauge) or less and above 12 ...
403.1.1 Gas Piping Installations, Pipe Size and Pressure Limitations
pressures of 15 psig (103.4 kPa gauge) or more shall be in accordance with Appendix G.
Gas distribution piping operating at a pressure of over 1/2 psig (3.5 ...
403.1.1 Gas Piping Installations, Pipe Size and Pressure Limitations
All requirements for installation of gas distribution piping with operating pressures at 1/2 psig (3.5 kPa gauge) or less and above 1/2 psig (3.5 kPa ...
1305.8.4 Fuel-Oil Piping and Storage, Capacity
Construction documents shall include calculations demonstrating that the extension of the normal and emergency vent piping is adequately sized to provide ...
1210.2.1 Hydronic Piping, Design
information: 1.1. Size and location of all steam piping. 1.2 The operating pressures and temperatures. 1.3 The ...