1704.8 Pile Foundations
JUMP TO FULL CODE CHAPTER
Special inspections shall be performed during installation and testing of pile foundations as required by Table 1704.8. The approved soils report, required by Section 1802.2, and the documents prepared by the registered design professional in responsible charge shall be used to determine compliance.
VERIFICATION AND INSPECTION TASK | CONTINUOUS DURING TASK LISTED | PERIODICALLY DURING TASK LISTED | |
1. | Verify pile materials, sizes and lengths comply with the requirements. | X | - |
2. | Determine capacities of test piles and conduct additional load tests, as required. | X | - |
3. | Observe driving operations and maintain complete and accurate records for each pile. | X | - |
4. | Verify placement locations and plumbness, confirm type and size of hammer, record number of blows per foot of penetration, determine required penetrations to achieve design capacity, record tip and butt elevations and document any pile damage. | X | - |
5. | For steel piles, perform additional inspections in accordance with Section 1704.3. | - | - |
6. | For concrete piles and concrete-filled piles, perform additional inspections in accordance with Section 1704.4. | - | - |
7. | For specialty piles, perform additional inspections as determined by the registered design professional in responsible charge. | - | - |
8. | For augered uncased piles and caisson piles, perform inspections in accordance with Section 1704.9. | - | - |
Related Code Sections
1704.8 Structural Tests and Special Inspections, Pile Foundations
Special inspections shall be performed during installation and testing of pile foundations as required by Table 1704.8. The approved soils report ...
2010 Building Code of NY > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.8 Pile Foundations
1705.9 Special Inspections and Tests, Helical Pile Foundations
Continuous special inspections shall be performed during installation of helical pile foundations. The information recorded shall include ...
Building Code 2015 of New York State > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.9 Helical Pile Foundations
1705.9 Special Inspections and Tests, Helical Pile Foundations
Continuous special inspections shall be performed during installation of helical pile foundations. The information recorded shall include ...
2020 Building Code of New York State > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.9 Helical Pile Foundations
Section 1808 Soils and Foundations, Pier and Pile Foundations
-inch-diameter (305 mm) or less bored, grouted-in-place piles incorporating steel pipe (casing) and/or steel reinforcement. PIER FOUNDATIONS. Pier ...
1809.1 Soils and Foundations, Timber Piles
Timber piles shall be designed in accordance with the AFPA NDS ...
2010 Building Code of NY > 18 Soils and Foundations > 1809 Driven Pile Foundations > 1809.1 Timber Piles