1926.1427(k) Phase-In
JUMP TO FULL CODE CHAPTER
The provisions of this section became applicable on November 8, 2010, except for paragraphs (a)(2) and (f) of this section, which are applicable November 10, 2018.
When paragraph (a)(1) of this section is not applicable, all of the requirements in paragraphs (k)(2)(i) and (ii) of this section apply until November 10, 2018.
The employer must ensure that operators of equipment covered by this standard are competent to operate the equipment safely.
When an employee assigned to operate machinery does not have the required knowledge or ability to operate the equipment safely, the employer must train that employee prior to operating the equipment. The employer must ensure that each operator is evaluated to confirm that he/she understands the information provided in the training.
[75 FR 48156, August 9, 2010; 79 FR 57798, September 26, 2014; 82 FR 51998, November 9, 2017]
[75 FR 48156, August 9, 2010; 79 FR 57798, September 26, 2014; 82 FR 51998, November 9, 2017]
Related Code Sections
1926.1427(k) Cranes & Derricks in Construction, Phase-In
The provisions of this section became applicable on November 8, 2010, except for paragraphs (a)(2) and (f) of this section, which are applicable ...
OSHA 1926 Construction > CC Cranes & Derricks in Construction > 1926.1427 Operator Qualification and Certification > 1926.1427(k) Phase-In
1926.960(c)(1)(i) Electric Power Transmission and Distribution,
TABLE V-3-ELECTRICAL COMPONENT OF THE MINIMUM APPROACH DISTANCE (D; IN METERS) AT 5.1 TO 72.5 KV
Nominal voltage (kV) phase-to-phase ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.960 Working on or Near Exposed Energized Parts > 1926.960(c) Live Work > 1926.960(c)(1) Minimum Approach Distances > 1926.960(c)(1)(i)
1926.960(c) Electric Power Transmission and Distribution, Live Work
TABLE V-3-ELECTRICAL COMPONENT OF THE MINIMUM APPROACH DISTANCE (D; IN METERS) AT 5.1 TO 72.5 KV
Nominal voltage (kV) phase-to-phase ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.960 Working on or Near Exposed Energized Parts > 1926.960(c) Live Work
Subpart V Electric Power Transmission and Distribution, App B - Working on Exposed Energized Parts
Otherwise, C is 0.011. In Equation 1, the term a varies depending on whether the employee's exposure is phase-to-ground or phase-to-phase ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > V App B - Working on Exposed Energized Parts
1926.960 Electric Power Transmission and Distribution, Working on or Near Exposed Energized Parts
TABLE V-3-ELECTRICAL COMPONENT OF THE MINIMUM APPROACH DISTANCE (D; IN METERS) AT 5.1 TO 72.5 KV
Nominal voltage (kV) phase-to-phase ...
OSHA 1926 Construction > V Electric Power Transmission and Distribution > 1926.960 Working on or Near Exposed Energized Parts