2.1-3.4.5 Phase II Recovery Room(s) or Area
Go To Full Code Chapter
A minimum of one Phase II patient care station per Class 2 or Class 3 imaging, procedure, or operating room shall be provided.
Related Code Sections
2.1-3.4.5 Common Elements for Hospitals, Phase II Recovery Room(s) or Area
A minimum of one Phase II patient care station per Class 2 or Class 3 imaging, procedure, or operating room shall be provided ...
*2.1-3.7.1.4 Common Elements for Outpatient Facilities, Number of Patient Care Stations
Room) Section 2.1-3.7.5 (Phase II Recovery Room or Area) A2.1-3.7.1.4 Determining the number of patient care stations. When designing the pre ...
2.2-3.3.5.10 Specific Requirements for General Hospitals, Support Areas for Patients and Visitors
toilet room(s) shall be permitted to be shared if directly accessible to preoperative and Phase II recovery areas. Where pre ...
2.7-3.5.10.2 Specific Requirements for Outpatient Surgery Facilities, Patient Toilet Room
to preoperative and Phase II recovery areas.
(c) Where pre- and postoperative patient care stations that are single-patient rooms are used for airborne ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Pennsylvania > 2.7 Specific Requirements for Outpatient Surgery Facilities > *2.7-3 Patient Care and Diagnostic Areas > 2.7-3.5 Pre- And Postoperative Patient Care > 2.7-3.5.10 Support Areas for Patients and Visitors > 2.7-3.5.10.2 Patient Toilet Room
2.1-3.4 Common Elements for Hospitals, Pre- And Post-Procedure Patient Care
-3.4.4 (Phase I Post-Anesthetic Care Unit)
Section 2.1-3.4.5 (Phase II Recovery Room or Area)
A2.1-3.4.1.4 Determining the number of patient ...