// CODE SNIPPET
3007.2 Phase I Emergency Recall Operation
Go To Full Code Chapter
Actuation of any building fire alarm-initiating device shall initiate Phase I emergency recall operation on all fire service access elevators in accordance with the requirements in ASME A17.1/CSA B44. All other elevators shall remain in normal service unless Phase I emergency recall operation is manually initiated by a separate, required three-position, key-operated "Fire Recall" switch or automatically initiated by the associated elevator lobby, hoistway or elevator machine room smoke detectors. In addition, if the building also contains occupant evacuation elevators in accordance with Section 3008, an independent, three-position, key-operated "Fire Recall" switch conforming to the applicable requirements in ASME A17.1/CSA B44 shall be provided at the designated level for each fire service access elevator.
Related Code Sections
2.27.4.1 Electric Elevators, Phase I Emergency Recall Operation
, in the hoistway, or in an elevator machine room, a control space, or a control room (see 2.27.3.2) shall initiate Phase I Emergency Recall Operation ...
3008.2 Elevators and Conveying Systems, Phase I Emergency Recall Operation
evacuation elevators shall be used for occupant self-evacuation only in the normal elevator operating mode prior to Phase I Emergency Recall Operation ...
3007.2 Elevators and Conveying Systems, Phase I Emergency Recall Operation
Actuation of any building fire alarm-initiating device shall initiate Phase I emergency recall operation on all fire service access elevators ...
3.27.2 Hydraulic Elevators, Phase I Emergency Recall Operation Prior to Device Actuation
(a) If any of the devices specified in 3.27.1(a), (b), (c), or (d) is activated, while Phase I Emergency Recall Operation is in effect but before ...
2.27.3.1.5 Electric Elevators,
All "FIRE RECALL" switches shall be provided with an illuminated visual signal to indicate when Phase I Emergency Recall Operation is in effect ...