// CODE SNIPPET
1203.19.2 PEX-AL-PEX-To-Metal Connections
Related Code Sections
1203.16.2 Hydronic Piping, PEX-AL-PEX-To-Metal Connections
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PEX-AL-PEX pipe ...
2020 Minnesota Mechanical Code > 12 Hydronic Piping > 1203 Joints and Connections > 1203.16 Cross-Linked Polyethylene/Aluminum/Cross-Linked Polyethylene (PEX-AL-PEX) Pressure Pipe > 1203.16.2 PEX-AL-PEX-To-Metal Connections
1203.19.2 Hydronic Piping, PEX-AL-PEX-To-Metal Connections
Solder joints in a metal pipe shall not occur within 18 inches (457 mm) of a transition from such metal pipe to PEX-AL-PEX pipe ...
Minnesota Mechanical Code 2015 > 12 Hydronic Piping > 1203 Joints and Connections > 1203.19 Cross-Linked Polyethylene/Aluminum/Cross-Linked Polyethylene (PEX-AL-PEX) Pressure Pipe > 1203.19.2 PEX-AL-PEX-To-Metal Connections
P2906.12 Water Supply and Distribution, Cross-Linked Polyethylene/Aluminum/Crosslinked Polyethylene
Joints between polyethylene/aluminum/polyethylene (PE-AL-PE) and cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe ...
2020 Minnesota Residential Code > 29 Water Supply and Distribution > P2906 Materials, Joints and Connections > P2906.12 Cross-Linked Polyethylene/Aluminum/Crosslinked Polyethylene
P2906.5 Water Supply and Distribution, Water Distribution Pipe
(PEX-AL-PEX) pipe
ASTM F1281; ASTM F2262; CSA B137.10
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX ...
2020 Minnesota Residential Code > 29 Water Supply and Distribution > P2906 Materials, Joints and Connections > P2906.5 Water Distribution Pipe