8.6.5.15 Periodic Test Requirements — Category 3
Go To Full Code Chapter
NOTE: For test frequency, see 8.11.1.3.
8.6.5.15.1 Unexposed Portions of Pistons
Piston rods of roped water-hydraulic elevators shall be exposed, thoroughly cleaned, and examined for wear or corrosion. The piston rods shall be replaced if at any place the diameter is less than the root diameter of the threads (Item 5.11).
8.6.5.15.2 Pressure Vessels
Pressure vessels shall be checked to determine conformance with the applicable requirements, thoroughly cleaned, internally examined, and then subjected to a hydrostatic test at 150% of the working pressure for 1 min (3.24.4) (Item 2.33).
Related Code Sections
8.6.5.15 General Requirements, Periodic Test Requirements — Category 3
NOTE: For test frequency, see 8.11.1.3. Piston ...
1705.13 Special Inspections and Tests, Special Inspections for Seismic Resistance
assigned to Seismic Design Category C, D, E or F, periodic special inspection shall be required for both: Welding operations of elements of the seismic ...
1705.13.7 Special Inspections and Tests, Storage Racks
Category D, E or F shall be provided with periodic special inspection as required by Table 1705.13.7.
TABLE 1705.13.7
REQUIRED ...
8.6.4.20 General Requirements, Periodic Test Requirements — Category 5
is performed, the test shall stop the car and verify that the safeties will be capable of stopping an overspeeding car in accordance with the requirements ...
8.11.1.1.2 General Requirements, Periodic Tests
(a) Periodic tests as required in Section 8.6 shall be performed by elevator personnel that are qualified to perform such tests. These tests shall ...
Safety Code for Elevators and Escalators 2019 of Illinois > 8 General Requirements > 8.11 Periodic Inspections and Witnessing of Tests > 8.11.1 General Requirements for Periodic Inspections and Witnessing of Tests > 8.11.1.1 Persons Authorized to Make Periodic Inspections and Witness Tests > 8.11.1.1.2 Periodic Tests