(C) Performance Testing
JUMP TO FULL CODE CHAPTER
The ground-fault protection system shall be performance tested when first installed on site. This testing shall be conducted by a qualified person(s) using a test process of primary current injection, in accordance with instructions that shall be provided with the equipment. A written record of this testing shall be made and shall be available to the authority having jurisdiction.
Informational Note No. 1: Ground-fault protection that functions to open the service disconnect affords no protection from faults on the line side of the protective element. It serves only to limit damage to conductors and equipment on the load side in the event of an arcing ground fault on the load side of the protective element.
Informational Note No. 2: This added protective equipment at the service equipment may make it necessary to review the overall wiring system for proper selective overcurrent protection coordination. Additional installations of ground-fault protective equipment may be needed on feeders and branch circuits where maximum continuity of electric service is necessary.
Informational Note No. 3: Where ground-fault protection is provided for the service disconnect and interconnection is made with another supply system by a transfer device, means or devices may be needed to ensure proper ground-fault sensing by the ground-fault protection equipment.
Informational Note No. 4: See 517.17(A) for information on where an additional step of ground-fault protection is required for hospitals and other buildings with critical areas or life support equipment.
Related Code Sections
(C) Wiring and Protection, Performance Testing
The ground-fault protection system shall be performance tested when first installed on site. This testing shall be conducted by a qualified person(s ...
National Electrical Code 2020 of Minnesota > 2 Wiring and Protection > 230 Services > 230.95 Ground-Fault Protection of Equipment > (C) Performance Testing
(C) Wiring and Protection, Performance Testing
The arc energy reduction protection system shall be performance tested by primary current injection testing or another approved method when first ...
National Electrical Code 2020 of Minnesota > 2 Wiring and Protection > 240 Overcurrent Protection > 240.67 Arc Energy Reduction > (C) Performance Testing
507.16 Exhaust Systems, Performance Test
A performance test shall be conducted upon completion and before final approval of the installation of a ventilation system serving commercial ...
Minnesota Mechanical Code 2015 > 5 Exhaust Systems > 507 Commercial Kitchen Hoods > 507.16 Performance Test
6.5.7.2.4 Heating, Ventilating, and Air Conditioning, Performance Testing
An approved field test method shall be used to evaluate design airflow rates and demonstrate proper capture and containment performance of installed ...
Energy Standard for Buildings Except Low-Rise Residential Buildings 2016 of Minnesota > 6 Heating, Ventilating, and Air Conditioning > 6.5 Prescriptive Path > 6.5.7 Exhaust Systems > 6.5.7.2 Kitchen Exhaust Systems > 6.5.7.2.4 Performance Testing
(D) Special Conditions, Functional Performance Tests
A functional performance test program shall be established, documented, and executed upon complete installation of the critical system in order ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 708 Critical Operations Power Systems (COPS) > 708.8 Commissioning > (D) Functional Performance Tests