808.2.1 Performance Method
JUMP TO FULL CODE CHAPTER
For each of the octave frequency bands with center frequencies of 500, 1000, and 2000 Hz, the reverberation time (T60) shall not exceed the times specified below:
- 0.6 seconds in classrooms with volumes up to and including 10,000 cubic feet (285 m3).
- 0.7 seconds in classrooms with volumes of more than 10,000 cubic feet (285 m3), but less than 20,000 cubic feet (566 m3).
Reverberation times shall apply to fully-furnished, unoccupied classrooms. Reverberation times shall be field verified via measurements over a minimum 20 dB decay in each octave frequency band in accordance with ASTM E2235 listed in Section 106.2.13.
Related Code Sections
808.2.1 Special Rooms and Spaces, Performance Method
For each of the octave frequency bands with center frequencies of 500, 1000, and 2000 Hz, the reverberation time (T60) shall not exceed the times ...
Accessible and Usable Buildings and Facilities 2017 of South Carolina > 8 Special Rooms and Spaces > 808 Enhanced Acoustics for Classrooms > 808.2 Reverberation Time > 808.2.1 Performance Method
301.1.3 Provisions for All Compliance Methods, Performance Compliance Method
Repairs , alterations , additions , changes in occupancy and relocated buildings complying with Chapter 14 of this code shall be considered ...
2015 South Carolina Existing Building Code > 3 Provisions for All Compliance Methods > 301 Administration > 301.1 General > 301.1.3 Performance Compliance Method
1401.2.2 Performance Compliance Methods, Partial Change in Occupancy
Where a portion of the building is changed to a new occupancy classification and that portion is separated from the remainder of the building ...
2015 South Carolina Existing Building Code > 14 Performance Compliance Methods > 1401 General > 1401.2 Applicability > 1401.2.2 Partial Change in Occupancy
1401.2.3 Performance Compliance Methods, Additions
Additions to existing buildings shall comply with the requirements of the
South Carolina Building Code ,
South Carolina Residential Code ...
2015 South Carolina Existing Building Code > 14 Performance Compliance Methods > 1401 General > 1401.2 Applicability > 1401.2.3 Additions