// CODE SNIPPET
1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum)
Go To Full Code ChapterSee More
1324.1 Where Required
Inspection and testing shall be performed on components, or portions thereof, of new, piped medical gas or vacuum systems, additions, renovations, temporary installations, or repaired systems in accordance with Section 1324.2 through Section 1324.5.11, and certified in accordance with Section 1306.0.
1324.2 Breached Systems
All systems that are breached and components that are subject to additions, renovations, or replacement (e.g., new gas sources: bulk, manifolds, compressors, dryers, alarms) shall be inspected and tested. Systems shall be deemed breached at the point of pipeline intrusion by physical separation or by system component removal, replacement, or addition. Breached portions of the systems subject to inspection and testing shall be confined to only the specific altered zone and components in the immediate zone or area that is located upstream for vacuum systems and downstream for pressure gases at the point or area of intrusion. [NFPA 99:5.1.12.1.3 — 5.1.12.1.5]
1324.2.1 Reports
The inspection and testing reports shall be submitted directly to the party that contracted for the testing, who shall submit the report through channels to the responsible facility authority and any others that are required. Reports shall contain detailed listings of all findings and results. [NFPA 99:5.1.12.1.6, 5.1.12.1.7]
1324.3 Test Gas
The test gas shall be oil-free, dry nitrogen NF. [NFPA 99:5.1.12.2.1.2]
1324.4 Initial Piping Blowdown
Piping in medical gas and vacuum distribution systems shall be blown clear by means of oil-free, dry nitrogen NF after installation of the distribution piping but before installation of station outlet/inlet rough-in assemblies and other system components (e.g., pressure/vacuum alarm devices, pressure/vacuum indicators, pressure relief valves, manifolds, source equipment). [NFPA 99:5.1.12.2.2]
1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems
Each section of the piping in medical gas and vacuum systems shall be pressure tested. Initial pressure tests shall be conducted as follows:
- After blowdown of the distribution piping.
- After installation of station outlet/inlet rough-in assemblies.
- Prior to the installation of components of the distribution piping system that would be damaged by the test pressure (e.g., pressure/vacuum alarm devices, pressure/vacuum indicators, line pressure relief valves). [NFPA 99:5.1.12.2.3.1, 5.1.12.2.3.2]
1324.5.1 Shutoff Valve
The source shutoff valve shall remain closed during tests specified in Section 1324.5 through Section 1324.5.1.2. [NFPA 99:5.1.12.2.3.3]
1324.5.1.1 Required Test Pressure
The test pressure for pressure gases and vacuum systems shall be 1.5 times the system operating pressure but not less than a gauge pressure of 150 psi (1034 kPa). The test pressure shall be maintained until each joint has been examined for leakage by means of a leak detectant that is safe for use with oxygen and does not contain ammonia. [NFPA 99:5.1.12.2.3.4, 5.1.12.2.3.5]
1324.5.1.2 Leaks
Leaks, if any, shall be located, repaired (if permitted), replaced (if required), and retested. [NFPA 99:5.1.12.2.3.6]
1324.5.2 Initial Cross-Connection Test
It shall be determined that no cross-connections exist between the various medical gas and vacuum piping systems. [NFPA 99:5.1.12.2.4]
1324.5.2.1 Atmospheric Pressure
All piping systems shall be reduced to atmospheric pressure. [NFPA 99:5.1.12.2.4.1]
1324.5.2.2 Sources of Test Gas
Sources of test gas shall be disconnected from all piping systems, except for the one system being tested. [NFPA 99:5.1.12.2.4.2]
1324.5.2.3 System to Be Charged
The system under test shall be charged with oil-free, dry nitrogen NF to a gauge pressure of 50 psi (345 kPa). [NFPA 99:5.1.12.2.4.3]
1324.5.2.4 Check Outlets and Inlets
After the installation of the individual faceplates with appropriate adapters matching outlet/inlet labels, each individual outlet/inlet in each installed medical gas and vacuum piping system shall be checked to determine that the test gas is being dispensed only from the piping system being tested. [NFPA 99:5.1.12.2.4.4]
1324.5.2.5 Repeat Test
The cross-connection test referenced in Section 1324.5.2 shall be repeated for each installed medical gas and vacuum piping system. [NFPA 99:5.1.12.2.4.5]
1324.5.2.6 Identification of System
The proper labeling and identification of system outlets/inlets shall be confirmed during these tests. [NFPA 99:5.1.12.2.4.6]
1324.5.3 Initial Piping Purge Tests
The outlets in each medical gas piping system shall be purged to remove any particulate matter from the distribution piping. [NFPA 99:5.1.12.2.5]
1324.5.3.1 Procedure
Using appropriate adapters, each outlet shall be purged with an intermittent high-volume flow of test gas until the purge produces no discoloration in a clean white cloth. [NFPA 99:5.1.12.2.5.1]
1324.5.3.2 Location
The purging required in Section 1324.5.3.1 shall be started at the closest outlet/inlet to the zone valve and continue to the furthest outlet/inlet within the zone. [NFPA 99:5.1.12.2.5.2]
1324.5.4 Standing Pressure Tests — For Positive Pressure Medical Gas Piping Systems
After successful completion of the initial pressure tests under Section 1324.5 through Section 1324.5.1.2, medical gas distribution piping shall be subjected to a standing pressure test. [NFPA 99:5.1.12.2.6]
1324.5.4.1 Time Frame for Testing
Tests shall be conducted after the final installation of station outlet valve bodies, faceplates, and other distribution system components (e.g. pressure alarm devices, pressure indicators, line pressure relief valves, manufactured assemblies, hose). [NFPA 99:5.1.12.2.6.1]
1324.5.4.2 Source Valve
The source valve shall be closed during this test. [NFPA 99:5.1.12.2.6.2]
1324.5.4.3 Length of Testing
The piping systems shall be subjected to a 24 hour standing pressure test using oil-free, dry nitrogen NF. [NFPA 99:5.1.12.2.6.3]
1324.5.4.4 Test Pressure
1324.5.4.5 Conclusion of Test
The leakage over the 24 hour test shall not exceed 0.5 percent of the starting pressure [e.g., 0.3 psi (2 kPa) starting at 60 psig (414 kPa), 0.125 inch (3.2 mm) HgV starting at 25 inches (635 mm) HgV] except that attributed to specific changes of ambient temperature. [NFPA 99:5.1.12.2.6.5]
1324.5.4.6 Leaks
Leaks, if any, shall be located, repaired (if permitted) or replaced (if required), and retested. [NFPA 99:5.1.12.2.6.6]
1324.5.4.7 Proof of Testing
The 24 hour standing pressure test of the positive pressure system shall be witnessed by an ASSE 6020 inspector, an ASSE 6030 verifier, or the Authority Having Jurisdiction or its designee. A form indicating that this test has been performed and witnessed shall be provided to the verifier at the start of the tests required in Section 1324.5.7 through Section 1324.5.11. [NFPA 99:5.1.12.2.6.7]
1324.5.5 Standing Pressure Tests — Medical Vacuum Piping Systems
After successful completion of the initial pressure tests under Section 1324.5 through Section 1324.5.1.2, vacuum distribution piping shall be subjected to a standing vacuum test. [NFPA 99:5.1.12.2.7]
1324.5.5.1 Timeframe for Testing
Tests shall be conducted after installation of all components of the vacuum system. [NFPA 99:5.1.12.2.7.1]
1324.5.5.2 Length of Testing
The piping systems shall be subjected to a 24 hour standing vacuum test. [NFPA 99:5.1.12.2.7.2]
1324.5.5.3 Test Pressure
1324.5.5.4 Disconnection of Testing Source
During the test, the source of test vacuum shall be disconnected from the piping system. [NFPA 99:5.1.12.2.7.4]
1324.5.5.5 Conclusion of Test
At the conclusion of the test, there shall be no change in the vacuum other than that attributed to changes of ambient temperature. [NFPA 99:5.1.12.2.7.5]
1324.5.5.6 Proof of Testing
The 24 hour standing pressure test of the vacuum system shall be witnessed by the Authority Having Jurisdiction or its designee. A form indicating that this test has been performed and witnessed shall be provided to the verifier at the start of the tests required in Section 1324.5.7 through Section 1324.5.11. [NFPA 99:5.1.12.2.7.6]
1324.5.5.7 Leaks
Leaks, if any, shall be located, repaired (if permitted) or replaced (if required), and retested. [NFPA 99:5.1.12.2.7.7]
1324.5.6 System Inspection
System inspections shall be performed prior to concealing piping distribution systems in walls, ceilings, chases, trenches, underground, or otherwise hidden from view. [NFPA 99:5.1.12.3.1.1]
1324.5.6.1 Test Gas
The test gas shall be nitrogen NF. [NFPA 99:5.1.12.3.1.2]
1324.5.6.2 Inspection Qualification
Inspections shall be conducted by a party technically competent and experienced in the field of medical gas and vacuum pipeline inspections and testing and meeting the requirements of ASSE 6020, or ASSE 6030. [NFPA 99:5.1.12.3.1.3]
1324.5.6.3 Inspection Personnel
Inspections shall be performed by a party other than the installing contractor. [NFPA 99:5.1.12.3.1.4]
1324.5.6.4 Qualifications
Where systems have not been installed by inhouse personnel, inspections shall be permitted by personnel of the organization who meet the requirements of Section 1324.5.6.2. [NFPA 99:5.1.12.3.1.5]
1324.5.6.5 Inspections
The initial pressure tests performed by the installing contractor shall be witnessed by an ASSE 6020 inspector, an ASSE 6030 verifier, or the Authority Having Jurisdiction or its designee. A form indicating that this test has been performed and witnessed shall be provided to the verifier at the start of the tests required in Section 1324.5.7 through Section 1324.5.11. The presence and correctness of labeling and valve tagging required by this code for all concealed components and piping distribution systems shall be inspected. [NFPA 99:5.1.12.3.2 — 5.1.12.3.2.2]
1324.5.7 System Verification
Verification tests shall be performed only after all tests required in Section 1324.3 through Section 1324.5.5.7, Installer Performed Tests, have been completed. [NFPA 99:5.1.12.4.1.1]
1324.5.7.1 Test Gas
The test gas shall be oil-free, dry nitrogen NF or the system gas where permitted. [NFPA 5.1.12.4.1.2]
1324.5.7.2 Approved Tester
Testing shall be conducted by a party technically competent and experienced in the field of medical gas and vacuum pipeline testing and meeting the requirements of ASSE 6030, except as required by Section 1324.5.7.3. [NFPA 99:5.1.12.4.1.3]
Testing shall be performed by a party other than the installing contractor. [NFPA 99:5.1.12.4.1.5]
Where systems have not been installed by inhouse personnel, testing shall be permitted by personnel of that organization who meet the requirements of Section 1324.5.7.2. [NFPA 99:5.1.12.4.1.6]
1324.5.7.3 Cryogenic Fluid Testing
Testing of the cryogenic fluid central supply system shall be conducted by a party technically competent and experienced in the field of cryogenic fluid systems and meeting the requirements of ASSE 6035, in accordance with the mandatory requirements in CGA M-1. [NFPA 99:5.1.12.4.1.4]
1324.5.8 Particulate Matter
In order to remove any traces of particulate matter deposited in the pipelines as a result of construction, a heavy, intermittent purging of the pipeline shall be done. [NFPA 99:5.1.12.4.6]
1324.5.9 Final Tie-in Test
Each joint in the final connection between the new work and the existing system shall be leak-tested with the gas of system designation at the normal operating pressure by means of a leak detectant that is safe for use with oxygen and does not contain ammonia. [NFPA 99:5.1.12.4.9.2]
1324.5.9.1 Vacuum Joints
1324.5.9.2 Pressure Gases
For pressure gases, immediately after the final brazed connection is made and leak-tested, an outlet in the new piping and an outlet in the existing piping that are immediately downstream from the point or area of intrusion shall be purged in accordance with the applicable requirements of Section 1324.5.8. [NFPA 99:5.1.12.4.9.4]
1324.5.9.3 Positive Pressure Gases
Before the new work is used for patient care, positive pressure gases shall be tested for operational pressure and gas concentration in accordance with Section 1324.5.10 and Section 1324.5.11. [NFPA 99:5.1.12.4.9.5]
1324.5.9.4 Permanent Records
Permanent records of these tests shall be maintained in accordance with NFPA 99. [NFPA 99:5.1.12.4.9.6]
1324.5.10 Operational Flow Pressure Drop Test
Operational flow pressure drop tests shall be performed at each station outlet/inlet or terminal where the user makes connections and disconnections. [NFPA 99: 5.1.12.4.10]
1324.5.10.1 Medical-Surgical Vacuum Inlets
Medical-surgical vacuum inlets shall draw 3 SCFM (85 Nl/min) without reducing the vacuum pressure below 12 inch (305 mm) gauge HgV at any adjacent station inlet. [NFPA 99:5.1.12.4.10.4]
1324.5.10.2 Oxygen and Medical Air Outlets
Oxygen and medical air outlets serving Category 1 space shall allow a transient flow rate of 6 SCFM (170 SLPM) for 3 seconds. [NFPA 99:5.1.12.4.10.5]
Related Code Sections
1324.0 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum)
Inspection and testing shall be performed on components, or portions thereof, of new, piped medical gas or vacuum systems, additions, renovations ...
1324.2.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Reports
The inspection and testing reports shall be submitted directly to the party that contracted for the testing, who shall submit the report through ...
1324.5.10 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Operational Flow Pressure Drop Test
[NFPA 99: 5.1.12.4.10] Medical-surgical vacuum ...
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.10 Operational Flow Pressure Drop Test
1324.5.11 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Medical Gas Concentration Test
Nitrogen NF
≤1% oxygen or ≥99% nitrogen
Medical air USP
19.5% - 23.5% oxygen
Other gases
Named gases by ±1%, or per ...
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.11 Medical Gas Concentration Test
1324.5.9 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Final Tie-in Test
] Vacuum joints shall be tested using an ultrasonic leak detector ...