5001.3 Performance-Based Design Alternative
JUMP TO FULL CODE CHAPTER
Where approved by the fire code official, buildings and facilities where hazardous materials are stored, used or handled shall be permitted to comply with this section as an alternative to compliance with the other requirements set forth in this chapter and Chapters 51 through 67.
The objective of Section 5001.3 is to protect people and property from the consequences of unauthorized discharge, fires or explosions involving hazardous materials.
Performance-based design alternatives are based on the following functional statements:
- Provide safeguards to minimize the risk of unwanted releases, fires or explosions involving hazardous materials.
- Provide safeguards to minimize the consequences of an unsafe condition involving hazardous materials during normal operations and in the event of an abnormal condition.
Where safeguards, systems, documentation, written plans or procedures, audits, process hazards analysis, mitigation measures, engineering controls or construction features are required by Sections 5001.3.3.1 through 5001.3.3.18, the details of the design alternative shall be subject to approval by the fire code official. The details of actions granting the use of the design alternatives shall be recorded and entered in the files of the jurisdiction.
The physical- and health-hazard properties of hazardous materials on site shall be known and shall be made readily available to employees, neighbors and the fire code official.
Equipment and operations involving hazardous materials shall be designed, installed and maintained to ensure that they reliably operate as intended.
Safeguards shall be provided to minimize the risk of an unintentional reaction or release that could endanger people or property.
Spill containment systems or means to render a spill harmless to people or property shall be provided where a spill is determined to be a plausible event and where such an event would endanger people or property.
Safeguards shall be provided to minimize the risk of exposing combustible hazardous materials to unintended sources of ignition.
Safeguards shall be provided to minimize the risk of exposing hazardous materials to a fire or physical damage whereby such exposure could endanger or lead to the endangerment of people or property.
Safeguards shall be provided to minimize the risk of and limit damage from a fire or explosion involving explosive hazardous materials whereby such fire or explosion could endanger or lead to the endangerment of people or property.
Where a release of hazardous materials gas or vapor would cause immediate harm to persons or property, means of mitigating the dangerous effects of a release shall be provided.
Where a power supply is relied on to prevent or control an emergency condition that could endanger people or property, the power supply shall be from a reliable source.
Where ventilation is necessary to limit the risk of creating an emergency condition resulting from normal or abnormal operations, means of ventilation shall be provided.
Process hazard analyses shall be conducted to ensure reasonably the protection of people and property from dangerous conditions involving hazardous materials.
Written documentation of prestartup safety review procedures shall be developed and enforced to ensure that operations are initiated in a safe manner. The process of developing and updating such procedures shall involve the participation of affected employees.
Written documentation of operating procedures and procedures for emergency shut down shall be developed and enforced to ensure that operations are conducted in a safe manner. The process of developing and updating such procedures shall involve the participation of affected employees.
A written plan for management of change shall be developed and enforced. The process of developing and updating the plan shall involve the participation of affected employees.
A written emergency plan shall be developed to ensure that proper actions are taken in the event of an emergency, and the plan shall be followed if an emergency condition occurs. The process of developing and updating the plan shall involve the participation of affected employees.
Written procedures for investigation and documentation of accidents shall be developed, and accidents shall be investigated and documented in accordance with these procedures.
Where an accidental release of hazardous materials could endanger people or property, either on or off-site, an analysis of the expected consequences of a plausible release shall be performed and utilized in the analysis and selection of active and passive hazard mitigation controls.
Safety audits shall be conducted on a periodic basis to verify compliance with the requirements of this section.
Related Code Sections
320.3.11 General Requirements, Performance-Based Design Alternative
to comply with the performance-based design options in Section 5001.3 as an alternative to compliance with the other requirements set forth in this section ...
Fire Code 2021 of Colorado > 3 General Requirements > 320 Additive Manufacturing (3D Printing) > 320.3 Industrial Additive Manufacturing > 320.3.11 Performance-Based Design Alternative
5001.3 Hazardous Materials—General Provisions, Performance-Based Design Alternative
Performance-based design alternatives are based on the following functional statements: Provide ...
Fire Code 2021 of Colorado > 50 Hazardous Materials—General Provisions > 5001 General > 5001.3 Performance-Based Design Alternative
5001.3 Hazardous Materials—General Provisions, Performance-Based Design Alternative
Performance-based design alternatives are based on the following functional statements: Provide ...
Fire Code 2018 of Colorado > 50 Hazardous Materials—General Provisions > 5001 General > 5001.3 Performance-Based Design Alternative
5001.3.3.1 Hazardous Materials—General Provisions, Properties of Hazardous Materials
The physical- and health-hazard properties of hazardous materials on site shall be known and shall be made readily available to employees, neighbors ...
Fire Code 2018 of Colorado > 50 Hazardous Materials—General Provisions > 5001 General > 5001.3 Performance-Based Design Alternative > 5001.3.3 Performance Requirements > 5001.3.3.1 Properties of Hazardous Materials
5001.3.3.10 Hazardous Materials—General Provisions, Ventilation
Where ventilation is necessary to limit the risk of creating an emergency condition resulting from normal or abnormal operations, means of ventilation ...
Fire Code 2021 of Colorado > 50 Hazardous Materials—General Provisions > 5001 General > 5001.3 Performance-Based Design Alternative > 5001.3.3 Performance Requirements > 5001.3.3.10 Ventilation