// CODE SNIPPET
Section A5.203 Performance Approach
JUMP TO FULL CODE CHAPTER
Nonresidential, high-rise residential and hotel/motel buildings that include lighting and/or mechanical systems shall comply with Sections A5.203.1.1 and A5.203.1.2. Newly constructed buildings and additions are included in the scope of these sections. Buildings permitted without lighting or mechanical systems shall comply with Section A5.203.1.1 but are not required to comply with Section A5.203.1.2.
To comply with Tier 1, ONE of the following efficiency measures is required for all applicable components of the building project. To comply with Tier 2, TWO of the following efficiency measures are required.
Newly installed out door lighting power shall be no greater than 90 percent of the Allowed Outdoor Lighting Power, and general hardscape lighting within the scope of Title 24, Part 6, Section 140.7(b)1 shall have a color temperature no higher than 3000K. The Allowed Outdoor Lighting Power calculation is specified in Title 24, Part 6, Section 140.7, Requirements For Outdoor Lighting.
Exception: The color temperature requirement is
not applicable to the applications identified in the
exceptions to Section 140.7(a) nor to the applications identified as "specific applications" in Section
140.7(b)2 and Table 140.7.
Newly constructed restaurants 8,000 square feet or greater and with service water heaters rated 75,000 Btu/h or greater shall install a solar water-heating system with a minimum solar savings fraction of 0.15.
Exceptions:
- Buildings with a natural gas service water heater with a minimum of 95-percent thermal efficiency.
- Buildings where greater than 75 percent of the total roof area has annual solar access that is less than 70 percent. Solar access is the ratio of solar insolation, including shade, to the solar insolation without shade. Shading from obstructions located on the roof or any other part of the building shall not be included in the determination of annual solar access.
Exterior
loading dock doors that are adjacent to conditioned or
indirectly conditioned spaces shall have dock seals or
dock shelters installed at the time of permitting. This
requirement shall apply to newly constructed buildings
and to loading dock doors added to existing buildings.
Daylighting devices shall be installed
as specified in Title 24, Part 6, Section 140.3(d).
Heat recovery requirements based on ASHRAE 90.1, Section 6.5.6.1 are adapted and modified for California climate zones as described below.
- Systems with minimum design outdoor air fraction of 80 percent or greater and supply air flow of 200 cfm or greater in climate zones 2, 9, 10, 11, 12, 13, 14, 15 shall have a heat recovery system.
- Heat recovery systems required by this section shall result in a net sensible energy recovery ratio of at least 60 percent for both heating and cooling as tested using AHRI 1060-2014 or 1061-2014 and certified by AHRI. A 60 percent sensible energy recovery ratio shall mean a change in the dry-bulb of the outdoor air supply equal to 60 percent of the difference between the outdoor air and exhaust air dry-bulb at design conditions. Provisions shall be made to bypass or control the energy recovery system to permit air economizer operation as required by Title 24, Part 6, Section 140.4(e), Economizers.
Exceptions:
- Systems serving spaces that are not cooled and that are heated to less than 60°F.
- Where more than 60 percent of the outdoor air heating energy is provided from site-recovered energy.
- Where the sum of the airflow rates exhausted
and relieved within 20 feet of each other is less than 75 percent of the design outdoor air-
flow rate, excluding exhaust air that is:
- Used for another energy recovery system;
- Not allowed by ASHRAE Standard 170 for use in energy recovery systems with leakage potential; or
- Of Class 4 as defined in ASHRAE Standard 62.1.
- Systems expected to operate less than 20 hours per week.
Comply with one of the advanced efficiency levels indicated below.
Buildings complying with the first level of advanced energy efficiency shall have an Energy Budget that is no greater than indicated below, depending on building type and the type of energy systems included in the building project. If the newly constructed building or addition does not include indoor lighting or mechanical systems, then no additional performance requirements above Title 24, Part 6 are required.
- For nonresidential building projects that include indoor lighting or mechanical systems, but not both: No greater than 95 percent of the Title 24, Part 6, Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
- For nonresidential building projects that include indoor lighting and mechanical systems: No greater than 90 percent of the Title 24, Part 6 Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
- For high-rise residential and hotel/motel building projects: No greater than 95 percent of the Title 24, Part 6, Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
Buildings complying with the second level of advanced energy efficiency shall have an Energy Budget that is no greater than indicated below, depending on building type and the type of energy systems included in the building project. If the newly constructed building or addition does not include indoor lighting or mechanical systems, then no additional performance requirements above Title 24, Part 6 are required.
- For nonresidential building projects that include indoor lighting or mechanical systems, but not both: No greater than 90 percent of the Title 24, Part 6, Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
- For nonresidential building projects that include indoor lighting and mechanical systems: No greater than 85 percent of the Title 24, Part 6, Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
- For high-rise residential and hotel/motel building projects: No greater than 95 percent of the Title 24, Part 6, Energy Budget for the Standard Design Building as calculated by compliance software certified by the Energy Commission.
Note: For Energy Budget calculations, high-rise residential and hotel/motel buildings are considered nonresidential buildings.
Related Code Sections
Section A5.203 Nonresidential Voluntary Measures, Performance Approach
, then no additional performance requirements above Title 24, Part 6 are required. For building projects that include indoor lighting or mechanical systems ...
California Green Building Standards Code 2016 > A5 Nonresidential Voluntary Measures > A5.203 Performance Approach
Section A5.203 Nonresidential Voluntary Measures, Performance Approach
lighting or mechanical systems, then no additional performance requirements above Title 24, Part 6 are required.
For nonresidential building projects ...
California Green Building Standards Code 2019 > A5 Nonresidential Voluntary Measures > A5.203 Performance Approach
Section A5.203 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Performance Approach
It is the intent of this code to encourage green buildings to achieve exemplary performance in the area of energy efficiency ...
California Green Building Standards Code 2016 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.203 Performance Approach
Section A5.203 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Performance Approach
It is the intent of this code to encourage green buildings to achieve exemplary performance in the area of energy efficiency ...
California Green Building Standards Code 2019 > A6.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4] > A5.203 Performance Approach
Section A4.204 Residential Voluntary Measures, Performance Approach for Additions
with no change to any mechanical system, then no additional performance requirements above Title 24, Part 6 are required. For one and only one ...
California Green Building Standards Code 2016 > A4 Residential Voluntary Measures > A4.204 Performance Approach for Additions