3203.9.2 Percentage of Group A Plastics
JUMP TO FULL CODE CHAPTER
The pallet, if any, shall not be included when measuring the weight of the commodity (WPU or WPE) or the volume of the commodity (VPE). The pallet, if any, shall be included when measuring the weight of the entire load (WL) or the volume of the entire load (VL).
Exception: Where noncombustible pallets are used, the pallets shall not be included in the volume and weight calculations.
The percentage by weight of Group A unexpanded plastics in the load shall be calculated in accordance with Equation 32-1.
The percentage by volume of Group A expanded plastics in the load shall be calculated in accordance with Equation 32-2.
The percentage by weight of Group A expanded plastics in the load shall be calculated in accordance with Equation 32-3.

(Equation-32-1)
where:

(Equation 32-2)
where:
VPE = Volume of Group A expanded plastic in the commodity, not including the volume of the pallet, if any.
VL = Volume of the entire load, including the volume of the pallet, if any.

(Equation 32-3)
where:
WPE = Weight of Group A expanded plastic in the commodity, not including the weight of the pallet, if any.
WL = Weight of the entire load, including the weight of the pallet, if any.
Related Code Sections
3203.9.2 High-Piled Combustible Storage, Percentage of Group A Plastics
pallets are used, the pallets shall not be included in the volume and weight calculations. The percentage by weight of Group A unexpanded plastics ...
Fire Code 2018 of Colorado > 32 High-Piled Combustible Storage > 3203 Commodity Classification > 3203.9 Limited Quantities of Group A Plastics in Mixed Commodities > 3203.9.2 Percentage of Group A Plastics
3203.9.2 High-Piled Combustible Storage, Percentage of Group A Plastics
plastics in the load shall be calculated in accordance with Equation 32-1.
The percentage by volume of Group A expanded plastics in the load shall ...
Fire Code 2021 of Colorado > 32 High-Piled Combustible Storage > 3203 Commodity Classification > 3203.9 Limited Quantities of Group A Plastics in Mixed Commodities > 3203.9.2 Percentage of Group A Plastics
Section 3203 High-Piled Combustible Storage, Commodity Classification
The percentage of Group A plastics determined in accordance with Section 3203.9.2 shall be used ...
Section 2607 Plastic, Light-Transmitting Plastic Wall Panels
Light-transmitting plastics shall not be used as wall panels in exterior walls in occupancies in Groups A-l, A-2, H, I-2 and I-3. In other groups ...
Section 2607 Plastic, Light-Transmitting Plastic Wall Panels
Light-transmitting plastics shall not be used as wall panels in exterior walls in occupancies in Groups A-1, A-2, H, I-2 and I-3. In other groups ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 26 Plastic > 2607 Light-Transmitting Plastic Wall Panels