507.3.1 Penetration
JUMP TO FULL CODE CHAPTER
Devices that require penetration of a Type I hood or grease duct, such as pipe and conduit penetration fittings and fasteners, shall be listed in accordance with UL 710 or UL 1978. Seams, joints, and penetrations of the hood enclosure shall comply with Section 508.3.2. Seams, joints, and penetrations of the ductwork shall comply with Section 510.5.3.
Related Code Sections
1009.3.1.5 Means of Egress, Penetrations
Penetrations in an exit access stairway enclosure shall be protected in accordance with Section 714 as required for fire barriers ...
Building Code 2012 of Nevada > 10 Means of Egress > 1009 Stairways > 1009.3 Exit Access Stairways > 1009.3.1 Construction > 1009.3.1.5 Penetrations
1022.5 Means of Egress, Penetrations
Penetrations into and openings through interior exit stairways and ramps are prohibited except for required exit doors, equipment and ductwork ...
Building Code 2012 of Nevada > 10 Means of Egress > 1022 Interior Exit Stairways and Ramps > 1022.5 Penetrations
1023.5 Means of Egress, Penetrations
Penetrations into or through interior exit stairways and ramps are prohibited except for the following: Equipment and ductwork necessary ...
Building Code 2018 of Nevada > 10 Means of Egress > 1023 Interior Exit Stairways and Ramps > 1023.5 Penetrations
1023.6 Means of Egress, Penetrations
Penetrations into and openings through an exit passageway are prohibited except for required exit doors, equipment and ductwork necessary ...
1024.6 Means of Egress, Penetrations
Penetrations into or through an exit passageway are prohibited except for the following: Equipment and ductwork necessary for independent ...