1228.30 Pediatric and Adolescent Psychiatric Unit
JUMP TO FULL CODE CHAPTER
Pediatric and adolescent psychiatric unit patient
areas shall be separate and distinct from adult psychiatric
unit patient areas. The requirements of Section 1228.14, Psychiatric
Nursing Service Space shall apply to pediatric and
adolescent units as amended below:
Maximum bedroom capacity
shall be four patients.
Patient bedroom areas
(with beds or cribs) shall meet the following requirements:
- Each patient shall have access to a toilet room, either from the patient room or from the corridor outside the patient room.
- Where access is provided via a corridor, the following
requirements shall be met:
- The combined area for activity space shall have 35 square feet (3.25 m2) of clear floor area per patient bed.
- A separate dining space shall be provided and shall have a minimum of 15 square feet (1.39 m2) of clear floor area per patient bed.
Pediatric and adolescent
outdoor areas shall be separate from adult outdoor
areas. Refer to Section 1228.13.1.2.
Storage space shall be provided for toys,
equipment, extra cribs and beds, and cots or recliners for
parents who may stay overnight.
Related Code Sections
1228.30 Interior Environment, Pediatric and Adolescent Psychiatric Unit
Pediatric and adolescent psychiatric unit patient
areas shall be separate and distinct from adult psychiatric
unit patient areas. The requirements ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.30 Pediatric and Adolescent Psychiatric Unit
1228.30.4 Interior Environment, Support Areas for the Pediatric and Adolescent Psychiatric Unit
Storage space shall be provided for toys,
equipment, extra cribs and beds, and cots or recliners for
parents who may stay overnight ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.30 Pediatric and Adolescent Psychiatric Service Space > 1228.30.4 Support Areas for the Pediatric and Adolescent Psychiatric Unit
1228.30.1.1 Interior Environment, Capacity
Maximum bedroom capacity
shall be four patients ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.30 Pediatric and Adolescent Psychiatric Unit > 1228.30.1 Patient Bedroom > 1228.30.1.1 Capacity
1228.30.1.2 Interior Environment, Space Requirements
Patient bedroom areas
(with beds or cribs) shall meet the following requirements:
For single-bed rooms, a minimum clear floor
area of 100 square ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.30 Pediatric and Adolescent Psychiatric Unit > 1228.30.1 Patient Bedroom > 1228.30.1.2 Space Requirements
1228.30.3.1 Interior Environment, Space Requirements
The combined area for activity space shall have
35 square feet (3.25 m 2 ) of clear floor area per
patient bed.
A separate dining space shall ...