1225.5.1.2.3 Patient Room Beds
JUMP TO FULL CODE CHAPTER
Patient rooms shall
be of such shape and dimensions to allow for the
performance of routine functions, including the easy
transfer of patients to and from bed to wheelchair or
wheeled stretcher. Patient rooms shall provide
direct access to a toilet room without entering or
passing through a patient bed area. Maximum occupancy
shall be two patients per patient room.
Exception: Where renovation of existing individual
patient rooms is undertaken in facilities built
under the 2013, or prior, California Building
Code, maximum room capacity shall be no more
than the present capacity, to a maximum of four
patients per patient room. Placement of beds
shall not be more than three deep from the exterior
window.
Related Code Sections
1225.5.1.2.3 Interior Environment, Patient Room Beds
to and from bed to wheelchair or
wheeled stretcher. Patient rooms shall provide
direct access to a toilet room without entering or
passing through a patient ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.2 Nursing Service Space > 1225.5.1.2.3 Patient Room Beds
1225.5.1.2.3 Interior Environment, Patient Room Beds
to and from bed to wheelchair or
wheeled stretcher. Patient rooms shall provide
direct access to a toilet room without entering or
passing through a patient ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.2 Nursing Service Space > 1225.5.1.2.3 Patient Room Beds
1225.5.1.2 Interior Environment, Nursing Service Space
, and fixed furnishings or
equipment.
Single-patient rooms: 110 square feet (10.21
m 2 ).
Multi-patient rooms: 80 square feet (7.43 m 2 )
per bed ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.5 Skilled Nursing Unit Models > 1225.5.1 Medical Model > 1225.5.1.2 Nursing Service Space
1225.4.1.6.2 Interior Environment, Toilet Rooms
than
two patient rooms, or eight beds.
...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1225 [OSHPD 2] Skilled Nursing and Intermediate-Care Facilities > 1225.4 Common Elements > 1225.4.1 Nursing Service Space > 1225.4.1.6 Toilet Room and Bath Facilities > 1225.4.1.6.2 Toilet Rooms
1224.14.1 Interior Environment, Patient Rooms
No patient room shall be
designed to accommodate more than four beds.
Exception: Where renovation of existing individual
patient rooms ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.14 Nursing Service Space > 1224.14.1 Patient Rooms