18.2.5.7.3.3 Patient Care Non-Sleeping Suite Travel Distance
Go To Full Code Chapter
(A)
Travel distance within a non-sleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m).