(A)
Travel distance within a non-sleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m).
(B)
Travel distance between any point in a non-sleeping suite and an exit shall not exceed 200 ft (61 m).

Related Code Sections

18.2.5 New Health Care Occupancies, Arrangement of Means of Egress
). Non-sleeping suites shall be in accordance with the following: Non-sleeping suites for patient care shall comply with the provisions ...
19.2.5.7 Existing Health Care Occupancies, Suites
be in accordance with the following: Non-sleeping suites for patient care shall comply with the provisions of 19.2.5.7.3.1 through 19.2.5.7.3.3 ...