1228.13.1 Patient Care Areas
JUMP TO FULL CODE CHAPTER
- At least two separate activity rooms, one appropriate for group recreation and one for quiet activities to serve as a patient lounge, shall be provided.
- Space requirements. The combined area of these rooms shall have a minimum of 25 square feet (2.32 m2) per patient bed, with at least 120 square feet (11.15 m2) of clear floor area for each of the two spaces.
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements:
- Fences and walls shall be designed to:
- Be installed with tamper-resistant hardware.
- Have a minimum height of 10 feet (3048 mm) above the outdoor area elevation.
- Be anchored and constructed to withstand the body force of a 350-pound (158-kg) person.
- If provided, gates or doors in the fence or wall
shall:
- Lights shall not be accessible to patients. Lighting in the outdoor activity area shall not be pole mounted.
- If provided, security cameras shall not be accessible to patients and cameras shall view the entire outdoor activity area.
- If provided, furniture shall be secured from movement. Furniture shall not be placed in locations where it can be used to climb the fence or wall.
- Space for staff conferences, patient evaluation
and progress reports.
- Where outpatients are treated, there shall be a waiting area compliant with the requirements of Section 1228.4.5.
Related Code Sections
1228.13.1 Interior Environment, Patient Care Areas
be
provided.
Space requirements. The combined area of these
rooms shall have a minimum of 25 square feet
(2.32 m 2 ) per patient bed, with at least 120 ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space > 1228.13.1 Patient Care Areas
1228.13.1 Interior Environment, Patient Care Areas
be
provided.
Space requirements. The combined area of these
rooms shall have a minimum of 25 square feet
(2.32 m 2 ) per patient bed, with at least 120 ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space > 1228.13.1 Patient Care Areas
517.81 Special Occupancies, Other-Than-Patient-Care Areas
In other-than-patient-care areas, installations shall be in accordance with the applicable provisions of other parts of this Code ...
California Electrical Code 2019 > 5 Special Occupancies > 517 Health Care Facilities > 517.81 Other-Than-Patient-Care Areas
1224.16.5 Interior Environment, Support Areas for Patient Care
A nurse station shall be provided in postoperative patient care areas, and shall allow direct observation of the patients and charting facilities ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.16 Anesthesia/Recovery Service Space > 1224.16.5 Support Areas for Patient Care
1224.16.5 Interior Environment, Support Areas for Patient Care
A nurse station shall be
provided in postoperative patient care areas, and
shall allow direct observation of the patients and
charting facilities ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.16 Anesthesia/Recovery Service Space > 1224.16.5 Support Areas for Patient Care