1204.2.1.1 Pathways to Ridge
JUMP TO FULL CODE CHAPTER
Not fewer than two 36-inch-wide (914 mm) pathways on separate roof planes, from lowest roof edge to ridge, shall be provided on all buildings. Not fewer than one pathway shall be provided on the street or driveway side of the roof. For each roof plane with a photovoltaic array, not fewer than one 36-inch-wide (914 mm) pathway from lowest roof edge to ridge shall be provided on the same roof plane as the photovoltaic array, on an adjacent roof plane or straddling the same and adjacent roof planes.
Related Code Sections
1204.2.1.1 Energy Systems, Pathways to Ridge
Not fewer than two 36-inch-wide (914 mm) pathways on separate roof planes, from lowest roof edge to ridge, shall be provided on all buildings. Not ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1204 Solar Photovoltaic Power Systems > 1204.2 Access and Pathways > 1204.2.1 Solar Photovoltaic Systems for Group R-3 Buildings > 1204.2.1.1 Pathways to Ridge
1205.2.1.1 Energy Systems, Pathways to Ridge
Not fewer than two 36-inch-wide (914 mm) pathways on separate roof planes, from lowest roof edge to ridge, shall be provided on all buildings. Not ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1205 Solar Photovoltaic Power Systems > 1205.2 Access and Pathways > 1205.2.1 Solar Photovoltaic (PV) Systems for Group R-3 Buildings > 1205.2.1.1 Pathways to Ridge
R324.6.2.1 Building Planning, Alternative Setback at Ridge
Where an automatic sprinkler system is installed within the dwelling in accordance with NFPA 13D or Section P2904, setbacks at ridges shall comply ...
Residential Code 2021 of Colorado > 3 Building Planning > R324 Solar Energy Systems > R324.6 Roof Access and Pathways > R324.6.2 Setback at Ridge > R324.6.2.1 Alternative Setback at Ridge