AF103.5 Passive Submembrane Depressurization System
JUMP TO FULL CODE CHAPTER
In buildings with crawl space foundations, the following components of a passive submembrane depressurization system shall be installed during construction.
Exception: Buildings in which an approved mechanical crawl space ventilation system or other equivalent system is installed.
Crawl spaces shall be provided with vents to the exterior of the building. The minimum net area of ventilation openings shall comply with Section R408.1.
The soil in crawl spaces shall be covered with a continuous layer of minimum 6-mil (0.15 mm) polyethylene soil-gas-retarder. The ground cover shall be lapped not less than 12 inches (305 mm) at joints and shall extend to all foundation walls enclosing the crawl space area.
A plumbing tee or other approved connection shall be inserted horizontally beneath the sheeting and connected to a 3- or 4-inch-diameter (76 or 102 mm) fitting with a vertical vent pipe installed through the sheeting. The vent pipe shall be extended up through the building floors, and terminate not less than 12 inches (305 mm) above the roof in a location not less than 10 feet (3048 mm) away from any window or other opening into the conditioned spaces of the building that is less than 2 feet (610 mm) below the exhaust point, and 10 feet (3048 mm) from any window or other opening in adjoining or adjacent buildings.
Related Code Sections
AF103.5 Radon Control Methods, Passive Submembrane Depressurization System
In buildings with crawl space foundations, the following components of a passive submembrane depressurization system shall be installed during ...
2018 Washington State Residential Code > F Radon Control Methods > AF103 Requirements > AF103.5 Passive Submembrane Depressurization System
AF103.5 Radon Control Methods, Passive Submembrane Depressurization System
In buildings with crawl space foundations, the following components of a passive submembrane depressurization system shall be installed during ...
2015 Washington State Residential Code > F Radon Control Methods > AF103 Requirements > AF103.5 Passive Submembrane Depressurization System
AF103.5.3 Radon Control Methods, Vent Pipe
A plumbing tee or other approved connection shall be inserted horizontally beneath the sheeting and connected to a 3- or 4-inch-diameter (76 or 102 ...
2015 Washington State Residential Code > F Radon Control Methods > AF103 Requirements > AF103.5 Passive Submembrane Depressurization System > AF103.5.3 Vent Pipe
Section AF103 Radon Control Methods, Requirements
, the following components of a passive submembrane depressurization system shall be installed during construction. Exception: Buildings in which ...
Section AF103 Radon Control Methods, Requirements
buildings with crawl space foundations, the following components of a passive submembrane depressurization system shall be installed during ...