• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

11B-503 Passenger Drop-Off and Loading Zones

California Building Code 2016 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-503 Passenger Drop-Off and Loading Zones
JUMP TO FULL CODE CHAPTER

11B-503.1 General

Passenger drop-off and loading zones shall comply with Section 11B-503.

11B-503.2 Vehicle Pull-Up Space

Passenger drop-off and loading zones shall provide a vehicular pull-up space 96 inches (2438 mm) wide minimum and 20 feet (6096 mm) long minimum.

11B-503.3 Access Aisle

Passenger drop-off and loading zones shall provide access aisles complying with Section 11B-503 adjacent and parallel to the vehicle pull-up space. Access aisles shall adjoin an accessible route and shall not overlap the vehicular way.
FIGURE 11B-503.3
PASSENGER DROP-OFF AND LOADING ZONE ACCESS AISLE

11B-503.3.1 Width

Access aisles serving vehicle pull-up spaces shall be 60 inches (1524 mm) wide minimum.

11B-503.3.2 Length

Access aisles shall extend the full length of the vehicle pull-up spaces they serve.

11B-503.3.3 Marking

Access aisles shall be marked with a painted borderline around their perimeter. The area within the borderlines shall be marked with hatched lines a maximum of 36 inches (914 mm) on center in a color contrasting with that of the aisle surface.

11B-503.4 Floor and Ground Surfaces

Vehicle pull-up spaces and access aisles serving them shall comply with Section 11B-302. Access aisles shall be at the same level as the vehicle pull-up space they serve. Changes in level are not permitted.
Exception: Slopes not steeper than 1:48 shall be permitted.

11B-503.5 Vertical Clearance

Vehicle pull-up spaces, access aisles serving them, and a vehicular route from an entrance to the passenger drop-off and loading zone and from the passenger drop-off and loading zone to a vehicular exit shall provide a vertical clearance of 114 inches (2896 mm) minimum.

Related Code Sections


11B-209.2.1 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Passenger Drop-Off and Loading Zones
Passenger drop-off and loading zones, except those required to comply with Sections 11B -209.2.2 and 11B -209.2.3, shall provide at least one ...
California Building Code 2016 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-209 Passenger Drop-Off and Loading Zones and Bus Stops > 11B-209.2 Type > 11B-209.2.1 Passenger Drop-Off and Loading Zones
11B-209.2.1 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Passenger Drop-Off and Loading Zones
Passenger drop-off and loading zones, except those required to comply with Sections 11B-209.2.2 and 11B-209.2.3, shall provide at least one passenger ...
California Building Code 2019 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-209 Passenger Drop-Off and Loading Zones and Bus Stops > 11B-209.2 Type > 11B-209.2.1 Passenger Drop-Off and Loading Zones
11B-503 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Passenger Drop-Off and Loading Zones
Passenger drop-off and loading zones shall comply with Section 11B -503 ...
California Building Code 2016 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-503 Passenger Drop-Off and Loading Zones
11B-503 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Passenger Drop-Off and Loading Zones
Passenger drop-off and loading zones shall comply with Section 11B-503 ...
California Building Code 2019 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-503 Passenger Drop-Off and Loading Zones
11B-209 Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing, Passenger Drop-Off and Loading Zones and Bus Stops
Passenger drop-off and loading zones shall be provided in accordance with Section 11B-209 ...
California Building Code 2019 (Vol 1 & 2) > 11B Accessibility to Public Buildings, Public Accommodations, Commercial Buildings and Public Housing > 11B-209 Passenger Drop-Off and Loading Zones and Bus Stops
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING