Section 6111 Parking and Garaging Oflp-Gas Tank Vehicles
JUMP TO FULL CODE CHAPTER
Exception: In cases of accident, breakdown or other emergencies, LP-gas tank vehicles are allowed to be parked and left unattended at any location while the operator is obtaining assistance.
The unattended parking of LP-gas tank vehicles shall be in accordance with Sections 6111.2.1 and 6111.2.2.
Exception: The unattended outdoor parking of LP-gas tank vehicles may also be in accordance with Section 9.7.2 of NFPA 58.
LP-gas tank vehicles shall not be left unattended at any time on residential streets or within 500 feet (152 m) of a residential area, apartment or hotel complex, educational facility, hospital or care facility. Tank vehicles shall not be left unattended at any other place that would, in the opinion of the fire code official, pose an extreme life hazard.
LP-gas tank vehicles parked at any one point for longer than 1 hour shall be located as follows:
Garaging of LP-gas tank vehicles shall be as specified in NFPA 58. Vehicles with LP-gas fuel systems are allowed to be stored or serviced in garages as specified in Section 11.16 of NFPA 58.
Related Code Sections
Section 6111 Liquefied Petroleum Gases, Parking and Garaging Oflp-Gas Tank Vehicles
Parking of LP-gas tank vehicles shall comply with Sections 6111.2 and 6111.3. Exception: In cases of accident, breakdown or other emergencies, LP ...
2012 Virginia Statewide Fire Prevention Code > 61 Liquefied Petroleum Gases > 6111 Parking and Garaging Oflp-Gas Tank Vehicles
6111.3 Liquefied Petroleum Gases, Garaging
Garaging of LP-gas tank vehicles shall be as specified in NFPA 58. Vehicles with LP-gas fuel systems are allowed to be stored or serviced in garages ...
2018 Virginia Statewide Fire Prevention Code > 61 Liquefied Petroleum Gases > 6111 Parking and Garaging of LP-gas Tank Vehicles > 6111.3 Garaging
6111.3 Liquefied Petroleum Gases, Garaging
Garaging of LP-gas tank vehicles shall be as specified in NFPA 58. Vehicles with LP-gas fuel systems are allowed to be stored or serviced in garages ...
2015 Virginia Statewide Fire Prevention Code > 61 Liquefied Petroleum Gases > 6111 Parking and Garaging of LP-gas Tank Vehicles > 6111.3 Garaging
6111.2 Liquefied Petroleum Gases, Unattended Parking
The unattended parking of LP-gas tank vehicles shall be in accordance with Sections 6111.2.1 and 6111.2.2. Exception: The unattended outdoor ...
2018 Virginia Statewide Fire Prevention Code > 61 Liquefied Petroleum Gases > 6111 Parking and Garaging of LP-gas Tank Vehicles > 6111.2 Unattended Parking