// CODE SNIPPET
§27-333 Parapets on Exterior Walls
JUMP TO FULL CODE CHAPTER
Parapets shall be provided on all exterior walls of buildings of construction class II-A, II-B, or II-C that have roof construction of combustible materials.
(a) Exceptions. A parapet need not be provided on the exterior wall of any building:
(1) That is less than twenty-two feet high; or
(2) Whose roof has a pitch of more than twenty degrees to the horizontal and whose overhang, fascia, cornice or gutter is of noncombustible construction, or if of combustible construction is separated from the roof and ceiling construction by construction having the fire-resistance rating required for the exterior wall of the building. Combustible members, excluding roof sheathing and its supporting members, if covered by a class A roof covering and complying with the restrictions as required by section 27-335 of this article, shall not extend through this construction, but shall have at least four inches of solid noncombustible material below, at the sides, and at the ends of such members; or
(3) That is provided with a fire canopy at, or not more than two feet below the roof level, continuous around that portion of the wall that is without a parapet, constructed as required by subdivision (f) of section 27-331 of this article.
(b) Construction. Parapets required under this section shall be of materials and assembly having at least the fire-resistance rating of the wall below, and shall be at least two feet high.
(a) Exceptions. A parapet need not be provided on the exterior wall of any building:
(1) That is less than twenty-two feet high; or
(2) Whose roof has a pitch of more than twenty degrees to the horizontal and whose overhang, fascia, cornice or gutter is of noncombustible construction, or if of combustible construction is separated from the roof and ceiling construction by construction having the fire-resistance rating required for the exterior wall of the building. Combustible members, excluding roof sheathing and its supporting members, if covered by a class A roof covering and complying with the restrictions as required by section 27-335 of this article, shall not extend through this construction, but shall have at least four inches of solid noncombustible material below, at the sides, and at the ends of such members; or
(3) That is provided with a fire canopy at, or not more than two feet below the roof level, continuous around that portion of the wall that is without a parapet, constructed as required by subdivision (f) of section 27-331 of this article.
(b) Construction. Parapets required under this section shall be of materials and assembly having at least the fire-resistance rating of the wall below, and shall be at least two feet high.
Related Code Sections
§27-333 Fire Protection Construction Requirements, Parapets on Exterior Walls
Parapets shall be provided on all exterior walls of buildings of construction class II-A, II-B, or II-C that have roof construction of combustible ...
NYC 1968 Code (Vol I) > 5 Fire Protection Construction Requirements > 4 Prevention of Exterior Fire Spread > §27-333 Parapets on Exterior Walls
704.11.1 Fire-Resistance-Rated Construction, Parapet Construction
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 704 Exterior Walls > 704.11 Parapets > 704.11.1 Parapet Construction
705.11.1 Fire and Smoke Protection Features, Parapet Construction
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.11 Parapets > 705.11.1 Parapet Construction
705.11.1 Fire and Smoke Protection Features, Parapet Construction
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have ...
NYC Building Code 2022 > 7 Fire and Smoke Protection Features > 705 Exterior Walls > 705.11 Parapets > 705.11.1 Parapet Construction
503.6.8 Chimneys and Vents, Exterior Wall Penetrations
A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 503 Venting of Equipment > 503.6 Gas Vents > 503.6.8 Exterior Wall Penetrations