Parapet walls shall be coped or covered in accordance with Sections 1503.3.1 and 1503.3.2. The top surface of the parapet wall shall provide positive drainage.
1503.3.1 Fire-Resistance-Rated Parapet Walls
Parapet walls required by Section 705.11 shall be coped or covered with weatherproof materials of a width not less than the thickness of the parapet wall such that the fire-resistance rating of the wall is not decreased.
1503.3.2 Other Parapet Walls
Parapet walls meeting one of the exceptions in Section 705.11 shall be coped or covered with weatherproof materials of a width not less than the thickness of the parapet wall.

Related Code Sections

1503.3 Roof Assemblies and Rooftop Structures, Parapet Walls
Parapet walls shall be coped or covered in accordance with Sections 1503.3.1 and 1503.3.2. The top surface of the parapet wall shall provide ...
1503.3 Roof Assemblies and Rooftop Structures, Coping
Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width not less than the thickness of the parapet wall ...
705.11.1 Fire and Smoke Protection Features, Parapet Construction
Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have ...