Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1010.2.9 Panic and Fire Exit Hardware

Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.2 Door Operations > 1010.2.9 Panic and Fire Exit Hardware
JUMP TO FULL CODE CHAPTER
Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware.
Exceptions:
  1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.2.4, Item 3.
  2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancy shall be permitted to be electrically locked in accordance with Section 1010.2.11 or  1010.2.12.
  3. Exit access doors serving occupied exterior areas shall be permitted to be locked in accordance with Section 1010.2.4, Item 8.
  4. Courtrooms shall be permitted to be locked in accordance with Section 1010.2.13, Item 3.

1010.2.9.1 Refrigeration Machinery Room

Refrigeration machinery rooms larger than 1,000 square feet (93 m2) shall have not less than two exit or exit access doorways that swing in the direction of egress travel and shall be equipped with panic hardware or fire exit hardware.

1010.2.9.2 Rooms With Electrical Equipment

ILLUSTRATION
Exit or exit access doors serving transformer vaults, rooms designated for batteries or energy storage systems, or modular data centers shall be equipped with panic hardware or fire exit hardware. Rooms containing electrical equipment rated 800 amperes or more that contain overcurrent devices, switching devices or control devices and where the exit or exit access door is less than 25 feet (7620 mm) from the equipment working space as required by NFPA 70, such doors shall not be provided with a latch or lock other than panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.

1010.2.9.3 Installation

Where panic or fire exit hardware is installed, it shall comply with the following:
  1. Panic hardware shall be listed in accordance with UL 305.
  2. Fire exit hardware shall be listed in accordance with UL 10C and UL 305.
  3. The actuating portion of the releasing device shall extend not less than one-half of the door leaf width.
  4. The maximum unlatching force shall not exceed 15 pounds (67 N).

1010.2.9.4 Balanced Doors

If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side.

Related Code Sections


804.5.4 Alterations—Level 2, Panic and Fire Exit Hardware
with an occupant load greater than 100, all required exit doors equipped with latching devices shall be equipped with approved panic or fire exit ...
Existing Building Code 2021 of Illinois > 8 Alterations—Level 2 > 804 Means of Egress > 804.5 Egress Doorways > 804.5.4 Panic and Fire Exit Hardware
1010.1.10 Means of Egress, Panic and Fire Exit Hardware
shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Exceptions: A main exit of a Group A occupancy shall ...
Building Code 2018 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.10 Panic and Fire Exit Hardware
1010.2.9 Means of Egress, Panic and Fire Exit Hardware
shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Exceptions: A main exit of a Group A occupancy shall ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.2 Door Operations > 1010.2.9 Panic and Fire Exit Hardware
1010.2.9.4 Means of Egress, Balanced Doors
If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.2 Door Operations > 1010.2.9 Panic and Fire Exit Hardware > 1010.2.9.4 Balanced Doors
1010.2.9.1 Means of Egress, Refrigeration Machinery Room
in the direction of egress travel and shall be equipped with panic hardware or fire exit hardware ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.2 Door Operations > 1010.2.9 Panic and Fire Exit Hardware > 1010.2.9.1 Refrigeration Machinery Room
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING