// CODE SNIPPET
909.16.1 Panel Indicators
JUMP TO FULL CODE CHAPTER
Fans within the building shall be shown on the fire-fighter's control panel. A clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control equipment, annunciated by fan and zone, and by pilot-lamp-type indicators as follows:
- Fans, dampers and other operating equipment in their normal status—WHITE.
- Fans, dampers and other operating equipment in their off or closed status—RED.
- Fans, dampers and other operating equipment in their on or open status—GREEN.
- Fans, dampers and other operating equipment in a fault status—YELLOW/AMBER.
Related Code Sections
909.16.1 Fire Protection Systems, Panel Indicators
Fans within the building shall be shown on the fire fighter's control panel. A clear indication of the direction of airflow and the relationship ...
NYC Building Code 2008 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire-Fighter's Smoke Control Panel > 909.16.1 Panel Indicators
909.16.1 Fire Protection Systems, Panel Indicators
Fans within the building shall be shown on the fire-fighter's control panel. A clear indication of the direction of airflow and the relationship ...
NYC Building Code 2014 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire-Fighter's Smoke Control Panel > 909.16.1 Panel Indicators
907.6.3.1 Fire Protection Systems, Zoning Indicator Panel
A zoning indicator panel and the associated controls shall be provided at the main building entrance accessible to responding Fire Department ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.6 Installation > 907.6.3 Zones > 907.6.3.1 Zoning Indicator Panel
907.8.1 Fire Protection Systems, Zoning Indicator Panel
A zoning indicator panel and the associated controls shall be provided at the main building entrance accessible to responding Fire Department ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.8 Zones > 907.8.1 Zoning Indicator Panel
911.1.5 Fire Protection Systems, Required Features
and water-flow detector display panels.
Emergency and standby power status indicators (generator running, generator failure to start).
Fire ...
NYC Building Code 2014 > 9 Fire Protection Systems > 911 Fire Command Center > 911.1 General > 911.1.5 Required Features