5.6.2 Pallet Types
JUMP TO FULL CODE CHAPTER
When loads are palletized, the use of wood or metal pallets, or listed pallets equivalent to wood, shall be assumed in the classification of commodities.
For Class I through Class IV commodities, when unreinforced polypropylene or unreinforced high-density polyethylene plastic pallets are used, the classification of the commodity unit shall be increased one class.
Unreinforced polypropylene or unreinforced high-density polyethylene plastic pallets shall be marked with a permanent symbol to indicate that the pallet is unreinforced.
For Class I through Class IV commodities, when reinforced polypropylene or reinforced high-density polyethylene plastic pallets are used, the classification of the commodity unit shall be increased two classes except for Class IV commodity, which shall be increased to a cartoned unexpanded Group A plastic commodity.
Pallets shall be assumed to be reinforced if no permanent marking or manufacturer's certification of nonreinforcement is provided.
No increase in the commodity classification shall be required for Group A plastic commodities stored on plastic pallets.
For ceiling-only sprinkler protection, the requirements of 5.6.2.2 and 5.6.2.3 shall not apply where plastic pallets are used and where the sprinkler system uses spray sprinklers with a minimum K-factor of K-16.8 (240).
The requirements of 5.6.2.2 through 5.6.2.7 shall not apply to nonwood pallets that have demonstrated a fire hazard that is equal to or less than wood pallets and are listed as such.
For Class I through Class IV commodities stored on plastic pallets when other than wood, metal, or polypropylene or high-density polyethylene plastic pallets are used, the classification of the commodity unit shall be determined by specific testing conducted by a national testing laboratory or shall be increased two classes.
Related Code Sections
315.7.5 General Requirements, Pallet Types
in accordance with UL 2335 or FM 4996. Plastic pallets shall be both solid and gridded deck, independent of the pallet manufacturing process, type ...
2020 Fire Code of NYS > 3 General Requirements > 315 General Storage > 315.7 Outdoor Pallet Storage > 315.7.5 Pallet Types
5.6.2 Classification of Occupancies and Commodities, Pallet Types
When loads are palletized, the use of wood or metal pallets, or listed pallets equivalent to wood, shall be assumed in the classification ...
Standard for the Installation of Sprinkler Systems 2013 of New York State > 5 Classification of Occupancies and Commodities > 5.6* Commodity Classification > 5.6.2 Pallet Types
5.6.2 Classification of Occupancies and Commodities, Pallet Types
When loads are palletized, the use of wood or metal pallets, or listed pallets equivalent to wood, shall be assumed in the classification ...
Standard for the Installation of Sprinkler Systems 2016 of New York State > 5 Classification of Occupancies and Commodities > 5.6* Commodity Classification > 5.6.2 Pallet Types
6.2.3.5 Escalators and Moving Walks, Pallet-Type Treadway
The treadway surface of each pallet shall be slotted in a direction parallel to its travel. Each slot shall be not more than 6.5 mm (0.25 in.) wide ...
Safety Code for Elevators and Escalators 2013 of New York State > 6 Escalators and Moving Walks > 6.2 Moving Walks > 6.2.3 Construction Requirements > 6.2.3.5 Pallet-Type Treadway
6.2.3.5 Escalators and Moving Walks, Pallet-Type Treadway
The treadway surface of each pallet shall be slotted in a direction parallel to its travel. Each slot shall be not more than 6.5 mm (0.25 in.) wide ...
Safety Code for Elevators and Escalators 2016 of New York State > 6 Escalators and Moving Walks > 6.2 Moving Walks > 6.2.3 Construction Requirements > 6.2.3.5 Pallet-Type Treadway