• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

905.11 Painting of Dedicated Standpipes

NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
JUMP TO FULL CODE CHAPTER
buildings bulletin
Linked Resources Available

This section has been clarified by a buildings bulletin issued by the Department of Buildings.

Learn more in the Linked Resources panel on the right.
Dedicated standpipes and the handles of valves serving standpipes shall be painted and such painting certified in accordance with Sections 905.11.1 through 905.11.6. In addition to painting, standpipe piping may also be identified by lettered legend in accordance with ANSI A13.1. Where the piping is required to be listed and labeled such painting shall not obscure such labeling.
Exceptions:
  1. Attachments, gauges, valves and operable parts of standpipes other than valve handles.
  2. Where different color coding may be required by Section 3406 of the New York City Fire Code for facilities storing, handling, and using flammable and combustible liquids in connection with special operations.

905.11.1 New Buildings

All portions of a standpipe system and the handles of valves serving the standpipe system in new buildings, including buildings constructed pursuant to Section 28-101.4.2 of the Administrative Code, shall be painted red prior to the hydrostatic pressure test whether or not they are intended to be enclosed at the end of construction.

905.11.2 Alterations

Existing handles of valves serving existing standpipe systems and existing unpainted standpipe risers that are exposed during alterations, including alterations pursuant to Section 28-101.4.2 of the Administrative Code shall be painted red. Where the alteration requires a hydrostatic pressure test such painting shall be completed prior to such test.

905.11.3 Retroactive Requirement for Completed Buildings

Notwithstanding any other provision of law, all portions of exposed standpipe systems and handles of valves serving the standpipe system of completed buildings in existence March 2, 2010 shall be painted red by June 2, 2010.

905.11.4 Buildings Under Construction

Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building or alteration of an existing building prior to March 2, 2010 and the work is not signed off by the department prior to such date, all exposed portions of the standpipe system and handles of valves serving the standpipe system shall be painted red prior to the hydrostatic pressure test, including portions that will be enclosed at a later point in time.
Exception: Portions of the standpipe system enclosed prior to March 2, 2010 need not be painted.

905.11.5 Combination Standpipe and Sprinkler Systems

Where a standpipe system that is used as a combination standpipe and sprinkler system is required to be painted pursuant to Section 905.11.1, 905.11.2, 905.11.3 or 905.11.4, the sprinkler risers and cross connections that are also used for the standpipe system shall be painted red, and the handles of valves serving such combination standpipe and sprinkler system shall be painted yellow.

905.11.6 Certification of Completion of System Painting

For all buildings where standpipe and combination sprinkler and standpipe systems are not subject to a special inspection pursuant to Section 1704.24 of this code, a licensed master plumber, licensed master fire suppression piping contractor, registered design professional or an individual holding an appropriate certificate of fitness from the Fire Department for the operation and/or maintenance of such system shall certify on forms provided by the department that all required painting has been completed in accordance with Section 905.11. Such certification shall be maintained on the premises and made available for inspection by the department and the Fire Department.

Related Code Sections


905.11 Fire Protection Systems, Painting of Dedicated Standpipes
Dedicated standpipes and the handles of valves serving standpipes shall be painted and such painting certified in accordance with Sections 905.11.1 ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
905.11 Fire Protection Systems, Painting of Dedicated Standpipes
Dedicated standpipes and the handles of valves serving standpipes shall be painted and such painting certified in accordance with Sections 905.11.1 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
905.11 Fire Protection Systems, Painting of Dedicated Standpipes
Dedicated standpipes and the handles of valves serving standpipes shall be painted and such painting certified in accordance with Sections 905.11.1 ...
NYC Building Code 2022 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes
905.11.5 Fire Protection Systems, Combination Standpipe and Sprinkler Systems
Where a standpipe system that is used as a combination standpipe and sprinkler system is required to be painted pursuant to Section 905.11.1 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes > 905.11.5 Combination Standpipe and Sprinkler Systems
905.11.2 Fire Protection Systems, Alterations
Existing handles of valves serving existing standpipe systems and existing unpainted standpipe risers that are exposed during alterations, including ...
NYC Building Code 2014 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.11 Painting of Dedicated Standpipes > 905.11.2 Alterations
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING