903.6 Painting of Dedicated Sprinkler Piping and Valve Handles
JUMP TO FULL CODE CHAPTER
Dedicated sprinkler piping shall be painted and such painting certified in accordance with Sections 903.6.1 through 903.6.5. In addition to painting, sprinkler piping may also be identified by lettered legend in accordance with ANSI A13.1. Where the piping is required to be listed and labeled such painting shall not obscure such labeling.
Exception:
- Attachments, gauges, valves and operable parts of sprinkler systems other than valve handles.
- Horizontal branch lines.
- Where different color coding may be required by Section 3406 of the New York City Fire Code for facilities storing, handling, and using flammable and combustible liquids in connection with special operations.
Cross connections and risers in new buildings, including buildings constructed pursuant to Section 28-101.4.2 of the Administrative Code, shall be painted red and the handles of valves serving dedicated sprinklers shall be painted green prior to the hydrostatic pressure test regardless of whether they will be enclosed at a later point in time.
Exception: Where a standpipe system is used as a combination standpipe and sprinkler system, the sprinkler risers and cross connections that are also used for the standpipe system shall be painted red and the handles of valves serving such combination system shall be painted yellow.
Cross connections and risers for independent (stand-alone) existing sprinkler systems that are exposed during alterations, including alterations pursuant to Section 28-101.4.2 of the Administrative Code, shall be painted red and the handles of valves serving such existing sprinkler systems shall be painted green. Where the alteration requires a hydrostatic pressure test such painting shall be completed prior to such test.
Exception: Where a standpipe system is used as a combination standpipe and sprinkler system, the sprinkler risers and cross connections that are also used for the standpipe system shall be painted red and the handles of valves serving such combination system shall be painted yellow.
Notwithstanding any other provision of law, all exposed risers and cross connections of completed buildings in existence on March 2, 2010 shall be painted red by June 2, 2010, and all handles of valves serving such sprinkler system shall be painted green.
Exception: Where a standpipe system is used as a combination standpipe and sprinkler system, the sprinkler risers and cross connections that are also used for the standpipe system shall be painted red and the handles of valves serving such combination system shall be painted yellow.
Notwithstanding any other provision of law, where construction documents were approved and permits issued for the construction of a new building or alteration of an existing building prior to March 2, 2010 and the work is not signed off by the department prior to such date, all exposed cross connections and risers in any such building shall be painted red prior to the hydrostatic pressure test, including cross connections and risers that will be enclosed at a later point in time, and handles of valves serving such sprinkler system shall be painted green.
Exception:
- Where a standpipe system is used as a combination standpipe and sprinkler system, the sprinkler risers and cross connections that are also used for the standpipe system shall be painted red and the handles of valves serving such combination system shall be painted yellow.
- Cross connections and risers enclosed prior to March 2, 2010 need not be painted.
For all buildings where sprinkler and combination sprinkler and standpipe systems are not subject to a special inspection pursuant to Section 1704.23 of this code, a licensed master plumber, licensed master fire suppression piping contractor, registered design professional or an individual holding an appropriate certificate of fitness from the Fire Department for the operation and/or maintenance of such system shall certify on forms provided by the department that all required painting has been completed in accordance with Section 903.6. Such certification shall be maintained on the premises and made available for inspection by the department and the Fire Department.
Related Code Sections
903.6 Fire Protection Systems, Painting of Dedicated Sprinkler Piping and Valve Handles
28-101.4.2 of the Administrative Code , shall be painted red and the handles of valves serving dedicated sprinklers shall be painted green prior ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles
903.6 Fire Protection Systems, Painting of Dedicated Sprinkler Piping and Valve Handles
to Section 28-101.4.2 of the Administrative Code , shall be painted red and the handles of valves serving dedicated sprinklers shall be painted green ...
NYC Building Code 2022 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles
903.6.2 Fire Protection Systems, Alterations
pursuant to Section 28-101.4.2 of the Administrative Code , shall be painted red and the handles of valves serving such existing sprinkler systems shall ...
NYC Building Code 2022 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles > 903.6.2 Alterations
903.6.4 Fire Protection Systems, Buildings Under Construction on March 2, 2010
that will be enclosed at a later point in time, and handles of valves serving such sprinkler system shall be painted green.
Exception:
Where a standpipe ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles > 903.6.4 Buildings Under Construction on March 2, 2010
903.6.4 Fire Protection Systems, Buildings Under Construction on March 2, 2010
that will be enclosed at a later point in time, and handles of valves serving such sprinkler system shall be painted green.
Exceptions:
Where ...
NYC Building Code 2022 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.6 Painting of Dedicated Sprinkler Piping and Valve Handles > 903.6.4 Buildings Under Construction on March 2, 2010