1406.2.2 Oxygen Trailers
JUMP TO FULL CODE CHAPTER
The storage and use of oxygen trailers shall be in accordance with FC 1406.2.2.1 through 1406.2.2.5.
Oxygen trailer containers shall be designed, constructed, tested and maintained in accordance with the United States Department of Transportation specifications and regulations.
Legible operating instructions shall be posted in the trailer and on or near any oxygen manifold used indoors.
Oxygen trailers shall at all times have affixed to them a motor vehicle license plate as issued in accordance with New York State or other applicable motor vehicle license plate laws, rules or regulations.
The owner or operator of an oxygen trailer shall notify the department, in writing, of the delivery of the trailer to a construction site, at least 48 hours in advance of such delivery. Such notification shall include:
- Contractor's name, address and telephone number.
- Location of the construction site.
- Quantity and frequency of oxygen delivery to the construction site.
- Expected duration of oxygen storage and use at the construction site.
The distance between oxygen trailers having a total aggregate capacity exceeding 20,000 SCF (566 m3) and exposures shall be in accordance with NFPA 55.
Related Code Sections
22.9.1.2 Special Occupancy Requirements,
For mobile acetylene trailer systems, a deluge sprinkler system shall be provided for MATS fire areas used as indoor and outdoor discharging stations ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 22 Special Occupancy Requirements > 22.9 Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes > 22.9.1 Design Requirements > 22.9.1.2
Section 1203 Special Piping and Storage Systems, Oxygen Systems
Nonmedical oxygen systems shall be designed and installed in accordance with NFPA 55 and NFPA 51 ...
Section 1203 Special Piping and Storage Systems, Oxygen Systems
Nonmedical oxygen systems shall be designed and installed in accordance with NFPA 50 and NFPA 51 ...
Section 1203 Special Piping and Storage Systems, Nonmedical Oxygen Systems
Nonmedical oxygen systems shall be designed and installed in accordance with NFPA 55 and NFPA 51 ...
22.10.1.2 Special Occupancy Requirements,
At mobile acetylene trailer systems (MATS) at mobile acetylene charging plants, a fire sprinkler system in accordance with this standard, Extra ...
Standard for the Installation of Sprinkler Systems 2016 of New York City > 22 Special Occupancy Requirements > 22.10 Acetylene Cylinder Charging Plants > 22.10.1 Design Requirements > 22.10.1.2