P2910.9.6 Overflow
JUMP TO FULL CODE CHAPTER
The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table P2910.9.6. The overflow outlet shall discharge at a point not less than 6 inches (152 mm) above the roof or roof drain; floor or floor drain; or over an open water-supplied fixture. The overflow outlet shall be covered with a corrosion-resistant screen of not less than 16 by 20 mesh per inch (630 by 787 mesh per m) and by 1/4-inch (6.4 mm) hardware cloth or shall terminate in a horizontal angle seat check valve. Drainage from overflow pipes shall be directed to prevent freezing on roof walks. The overflow drain shall not be equipped with a shutoff valve. Not less than one cleanout shall be provided on each overflow pipe in accordance with Section P3005.2.
Related Code Sections
1301.9.5 Nonpotable Water Systems, Overflow
The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table 606.5.4. The overflow pipe shall ...
Plumbing Code 2018 of Kansas > 13 Nonpotable Water Systems > 1301 General > 1301.9 Nonpotable Water Storage Tanks > 1301.9.5 Overflow
2405.3.1 Flammable Finishes, Overflow
Dip tanks greater than 150 gallons (568 L) in capacity or 10 square feet (0.93 m 2 ) in liquid surface area shall be equipped with a trapped overflow ...
Fire Code 2018 of Kansas > 24 Flammable Finishes > 2405 Dipping Operations > 2405.3 Construction of Dip Tanks > 2405.3.1 Overflow
P2910.9.6 Water Supply and Distribution, Overflow
The storage tank shall be equipped with an overflow pipe having a diameter not less than that shown in Table P2910.9.6. The overflow outlet shall ...
Residential Code 2018 of Kansas > 29 Water Supply and Distribution > P2910 Nonpotable Water Systems > P2910.9 Nonpotable Water Storage Tanks > P2910.9.6 Overflow
405.8 Fixtures, Faucets and Fixture Fittings, Design of Overflows
Where any fixture is provided with an overflow, the waste shall be designed and installed so that standing water in the fixture will not rise ...
Plumbing Code 2018 of Kansas > 4 Fixtures, Faucets and Fixture Fittings > 405 Installation of Fixtures > 405.8 Design of Overflows
415.3.2 Fixtures, Faucets and Fixture Fittings, Overflows in Flush Tanks
Flush tanks shall be provided with overflows discharging to the water closet or urinal connected thereto and shall be sized to prevent flooding ...
Plumbing Code 2018 of Kansas > 4 Fixtures, Faucets and Fixture Fittings > 415 Flushing Devices for Water Closets and Urinals > 415.3 Flush Tanks > 415.3.2 Overflows in Flush Tanks