3111F.9.2 Overfill Monitoring and Controls (N/E)
JUMP TO FULL CODE CHAPTER
Overfill protection systems shall conform to Appendix C of API Standard 2350 [11.10]. These systems shall be tested before each transfer operation or monthly, whichever is less frequent. Where vessel or barge overfill sensors and alarms are provided, they shall comply with 33 CFR 154.2102 [11.11].
All sumps shall be provided with level sensing devices to initiate an alarm to alert the operator at the approach of a high level condition. A second alarm shall be initiated at a high-high level to alert the operator. Unless gravity drainage is provided, sumps must have an automatic pump, programmed to start at a predetermined safe level.
Related Code Sections
3111F.9.2 [SLC] Marine Oil Terminals, Overfill Monitoring and Controls (N/E)
Overfill protection systems shall conform to Appendix C of API Standard 2350 [11.10]. These systems shall be tested before each transfer operation ...
California Building Code 2016 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3111F Electrical Systems > 3111F.9 Communications, Control and Monitoring Systems > 3111F.9.2 Overfill Monitoring and Controls (N/E)
3111F.9.2 [SLC] Marine Oil Terminals, Overfill Monitoring and Controls (N/E)
Overfill
protection systems shall conform to Appendix C of API
Standard 2350 [11.10]. These systems shall be tested
before each transfer operation ...
California Building Code 2019 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3111F Electrical Systems > 3111F.9 Communications, Control and Monitoring Systems > 3111F.9.2 Overfill Monitoring and Controls (N/E)
3111F.9.3 [SLC] Marine Oil Terminals, Monitoring Systems (N/E)
All monitoring systems
and instrumentation such as, but not limited to:
velocity monitoring systems, tension monitoring systems,
anemometers ...
California Building Code 2019 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3111F Electrical Systems > 3111F.9 Communications, Control and Monitoring Systems > 3111F.9.3 Monitoring Systems (N/E)
3108F.6.5 [SLC] Marine Oil Terminals, Fire Monitor Systems
provide at least two independent streams of water/foam. Monitors shall be located to provide an unobstructed path between the monitor and the target area (N ...
California Building Code 2016 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3108F Fire Prevention, Detection and Suppression > 3108F.6 Fire Suppression > 3108F.6.5 Fire Monitor Systems
3108F.6.5 [SLC] Marine Oil Terminals, Fire Monitor Systems
, in
order to determine if monitors located on elevated masts
or towers are required (N/E):
Maximum tanker freeboard
Tidal variations
Pier/wharf ...
California Building Code 2019 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3108F Fire Prevention, Detection and Suppression > 3108F.6 Fire Suppression > 3108F.6.5 Fire Monitor Systems