E3705.5.2 Overcurrent Devices of the Next Higher Rating
JUMP TO FULL CODE CHAPTER
The next higher standard overcurrent device rating, above the ampacity of the conductors being protected, shall be permitted to be used, provided that all of the following conditions are met:
- The conductors being protected are not part of a branch circuit supplying more than one receptacle for cord- and plug-connected portable loads.
- The ampacity of conductors does not correspond with the standard ampere rating of a fuse or a circuit breaker without overload trip adjustments above its rating (but that shall be permitted to have other trip or rating adjustments).
- The next higher standard device rating does not exceed 400 amperes. [240.4(B)]
Related Code Sections
E3705.5.2 Branch Circuit and Feeder Requirements, Overcurrent Devices of the Next Higher Rating
The next higher standard overcurrent device rating, above the ampacity of the conductors being protected, shall be permitted to be used, provided ...
Residential Code 2018 of Kansas > 37 Branch Circuit and Feeder Requirements > E3705 Conductor Sizing and Overcurrent Protection > E3705.5 Overcurrent Protection Required > E3705.5.2 Overcurrent Devices of the Next Higher Rating
E4101.4.1 Appliance Installation, Single Nonmotor-Operated Appliance
, the next higher standard rating shall be permitted. Where the overcurrent protection rating is not marked and the appliance is rated at 13.3 amperes ...
Residential Code 2018 of Kansas > 41 Appliance Installation > E4101 General > E4101.4 Overcurrent Protection > E4101.4.1 Single Nonmotor-Operated Appliance
(E) Equipment for General Use, Single Non-Motor-Operated Appliance
13.3 amperes. Where 150 percent of the appliance rating does not correspond to a standard overcurrent device ampere rating, the next higher standard ...
National Electrical Code 2017 of Kansas > 4 Equipment for General Use > 422 Appliances > 422.11 Overcurrent Protection > (E) Single Non-Motor-Operated Appliance
630.32 Special Equipment, Overcurrent Protection
device, a higher rating or setting that does not exceed the next higher standard ampere rating shall be permitted ...
National Electrical Code 2017 of Kansas > 6 Special Equipment > 630 Electric Welders > 630.32 Overcurrent Protection
(A) Equipment for General Use, Overcurrent Protection
or more, the next higher standard rating described in 240.6 shall be permitted. An overcurrent device shall not be installed in series with the shunt ...
National Electrical Code 2017 of Kansas > 4 Equipment for General Use > 450 Transformers and Transformer Vaults (Including Secondary Ties) > 450.4 Autotransformers 1000 Volts, Nominal, or Less > (A) Overcurrent Protection