E4207.3.2 Over the Low-Voltage Contact Limit but Not Over 150 Volts
JUMP TO FULL CODE CHAPTER
A lighting assembly without a transformer or power supply, and with the luminaire lamp(s) operating at over the low-voltage contact limit, but not over 150 volts, shall be permitted to be cord and plug-connected where the assembly is listed as an assembly for the purpose and complies with all of the following:
- It has an impact-resistant polymeric lens and luminaire body.
- A ground-fault circuit interrupter with open neutral conductor protection is provided as an integral part of the assembly.
- The luminaire lamp is permanently connected to the ground-fault circuit interrupter with open-neutral protection.
- It complies with the requirements of Section E4206.4.
- It has no exposed metal parts.
Related Code Sections
E4207.3.2 Swimming Pools, Over the Low-Voltage Contact Limit but Not Over 150 Volts
A lighting assembly without a transformer or power supply, and with the luminaire lamp(s) operating at over the low-voltage contact limit ...
2012 Virginia Residential Code > 42 Swimming Pools > E4207 Storable Swimming Pools > E4207.3 Luminaires > E4207.3.2 Over the Low-Voltage Contact Limit but Not Over 150 Volts
E4207.3.2 Swimming Pools, Over the Low-Voltage Contact Limit but Not Over 150 Volts
A lighting assembly without a transformer or power supply, and with the luminaire lamp(s) operating at over the low-voltage contact limit ...
2015 Virginia Residential Code > 42 Swimming Pools > E4207 Storable Swimming Pools, Storable Spas, and Storable Hot Tubs > E4207.3 Luminaires > E4207.3.2 Over the Low-Voltage Contact Limit but Not Over 150 Volts
E4206.4.1 Swimming Pools, Maximum Voltage
Luminaires shall not be installed for operation on supply circuits over 150 volts between conductors ...
2012 Virginia Residential Code > 42 Swimming Pools > E4206 Equipment Installation > E4206.4 Underwater Luminaires > E4206.4.1 Maximum Voltage
E4206.4.1 Swimming Pools, Maximum Voltage
Luminaires shall not be installed for operation on supply circuits over 150 volts between conductors. [680.23(A)(4)] ...
2015 Virginia Residential Code > 42 Swimming Pools > E4206 Equipment Installation > E4206.4 Underwater Luminaires > E4206.4.1 Maximum Voltage
E4206.4 Swimming Pools, Underwater Luminaires
be installed in the branch circuit supplying luminaires operating at more than the low-voltage contact limit, such that there is no shock hazard during ...
2015 Virginia Residential Code > 42 Swimming Pools > E4206 Equipment Installation > E4206.4 Underwater Luminaires