10.15* Outside Storage
JUMP TO FULL CODE CHAPTER
Outside storage of combustible materials shall not be located within 10 ft (3 m) of a property line.
The separation distance shall be allowed to be reduced to 3 ft (0.9 m) for storage not exceeding 6 ft (1.8 m) in height.
The separation distance shall be allowed to be reduced where the AHJ determines that no hazard to the adjoining property exists.
Combustible material shall not be stored beneath a building or structure unless specifically constructed or protected for this purpose.
Combustible storage in the open shall not exceed 20 ft (6.1 m) in height.