(A) Outside of Buildings
JUMP TO FULL CODE CHAPTER
Lead-in conductors attached to buildings shall be installed so that they cannot swing closer than 600 mm (2 ft) to the conductors of circuits of 250 volts or less between conductors, or 3.0 m (10 ft) to the conductors of circuits of over 250 volts between conductors, except that in the case of circuits not over 150 volts between conductors, where all conductors involved are supported so as to ensure permanent separation, the clearance shall be permitted to be reduced but shall not be less than 100 mm (4 in.). The clearance between lead-in conductors and any conductor forming a part of a lightning protection system shall not be less than 1.8 m (6 ft). Underground conductors shall be separated at least 300 mm (12 in.) from conductors of any light or power circuits or Class 1 circuits.
Exception: Where the electric light or power conductors, Class 1 conductors, or lead-in conductors are installed in raceways or metal cable armor.
Informational Note No. 1: See 250.60 for grounding associated with lightning protection components — strike termination devices. For further information, see NFPA 780-2017, Standard for the Installation of Lightning Protection Systems, which contains detailed information on grounding, bonding, and spacing from lightning protection systems, and the calculation of specific separation distances using the sideflash equation in Section 4.6.
Informational Note No. 2: Metal raceways, enclosures, frames, and other non-current-carrying metal parts of electrical equipment installed on a building equipped with a lightning protection system may require bonding or spacing from the lightning protection conductors in accordance with NFPA 780-2017, Standard for the Installation of Lightning Protection Systems. Separation from lightning protection conductors is typically 1.8 m (6 ft) through air or 900 mm (3 ft) through dense materials such as concrete, brick, or wood.
Related Code Sections
(A) Communications Systems, Outside of Buildings
Lead-in conductors attached to buildings shall be installed so that they cannot swing closer than 600 mm (2 ft) to the conductors of circuits of 250 ...
National Electrical Code 2020 of Minnesota > 8 Communications Systems > 810 Radio and Television Equipment > 810.18 Clearances — Receiving Stations > (A) Outside of Buildings
(B) Special Conditions, Terminating on the Outside of Buildings
on the outside of the building, the non-current-carrying metallic members shall be either grounded or bonded as specified in 770.100 or interrupted ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 770 Optical Fiber Cables > 770.93 Grounding, Bonding, or Interruption of Non-Current-Carrying Metallic Members of Optical Fiber Cables > (B) Terminating on the Outside of Buildings
(B) Communications Systems, Terminating on the Outside of Buildings
In installations where the communications cable is terminated on the outside of the building, the metallic sheath members of the cable shall ...
National Electrical Code 2020 of Minnesota > 8 Communications Systems > 800 General Requirements for Communications Systems > 805.93 Grounding, Bonding, or Interruption of Non-Currentcarrying Metallic Sheath Members of Communications Cables > (B) Terminating on the Outside of Buildings
C403.12.1 [CE] Commercial Energy Efficiency, Heating Outside a Building
Systems installed to provide heat outside a building shall be radiant systems. Such heating systems shall be controlled by an occupancy sensing ...
2020 Minnesota Energy Code > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.12 Mechanical Systems Located Outside of the Building Thermal Envelope (Mandatory) > C403.12.1 Heating Outside a Building
230.6 Wiring and Protection, Conductors Considered Outside the Building
Conductors shall be considered outside of a building or other structure under any of the following conditions: Where installed under not less than ...
National Electrical Code 2020 of Minnesota > 2 Wiring and Protection > 230 Services > 230.6 Conductors Considered Outside the Building