Section 904 Outdoor Vent Extensions
JUMP TO FULL CODE CHAPTER
The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors.
The required vent shall be a dry vent that connects to the building drain or an extension of a drain that connects to the building drain. Such vent shall not be an island fixture vent as allowed by Section 916.
The required vent shall be sized in accordance with Section 906.2 based on the required size of the building drain.
Vent stacks or stack vents shall terminate outdoors to the open air or to a stack-type air admittance valve in accordance with Section 918.
Vent stacks shall connect to the base of the drainage stack. The vent stack shall connect at or below the lowest horizontal branch. Where the vent stack connects to the building drain, the connection shall be located downstream of the drainage stack and within a distance of 10 times the diameter of the drainage stack.
Stack vents and vent stacks connected into a common vent header at the top of the stacks and extending to the open air at one point shall be sized in accordance with the requirements of Section 906.1. The number of fixture units shall be the sum of all fixture units on all stacks connected thereto, and the developed length shall be the longest vent length from the intersection at the base of the most distant stack to the vent terminal in the open air, as a direct extension of one stack.
Related Code Sections
Section 904 Vents, Outdoor Vent Extensions
The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors ...
904.1.1 Vents, Installation
The required vent shall be a dry vent that connects to the building drain or an extension of a drain that connects to the building drain . Such ...
Plumbing Code 2018 of Kansas > 9 Vents > 904 Outdoor Vent Extensions > 904.1 Required Vent Extension > 904.1.1 Installation
904.1.2 Vents, Size
The required vent shall be sized in accordance with Section 906.2 based on the required size of the building drain ...
Plumbing Code 2018 of Kansas > 9 Vents > 904 Outdoor Vent Extensions > 904.1 Required Vent Extension > 904.1.2 Size
903.2 Vents, Frost Closure
Where the 97.5-percent value for outdoor design temperature is 0°F (-18°C) or less, vent extensions through a roof or wall shall be not less than 3 ...
Section P3102 Vents, Vent Stacks and Stack Vents
The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors ...