6004.3.4 Outdoor Use of Cylinders, Containers and Portable Tanks
JUMP TO FULL CODE CHAPTER
Cylinders, containers and portable tanks in outdoor use shall be located in gas cabinets or exhausted enclosures and shall comply with Sections 6004.3.4.1 through 6004.3.4.3.
The treatment system requirements set forth in Section 6004.2.2.7 shall apply to highly toxic or toxic gases located outdoors.
The requirements for emergency power set forth in Section 6004.2.2.8 shall apply to highly toxic or toxic gases located outdoors.
The gas detection system requirements set forth in Section 6004.2.2.10 shall apply to highly toxic or toxic gases located outdoors.
Related Code Sections
6004.3.4 Highly Toxic and Toxic Materials, Outdoor Use of Cylinders, Containers and Portable Tanks
Cylinders, containers and portable tanks in outdoor use shall be located in gas cabinets or exhausted enclosures and shall comply with Sections ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.4 Outdoor Use of Cylinders, Containers and Portable Tanks
6004.3.4 Highly Toxic and Toxic Materials, Outdoor Use of Cylinders, Containers and Portable Tanks
Cylinders, containers and portable tanks in outdoor use shall be located in gas cabinets or exhausted enclosures and shall comply with Sections ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.4 Outdoor Use of Cylinders, Containers and Portable Tanks
6004.3.4.3 Highly Toxic and Toxic Materials, Gas Detection System
The gas detection system requirements set forth in Section 6004.2.2.10 shall apply to highly toxic or toxic gases located outdoors ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use > 6004.3.4 Outdoor Use of Cylinders, Containers and Portable Tanks > 6004.3.4.3 Gas Detection System
6004.3 Highly Toxic and Toxic Materials, Outdoor Storage and Use
Weather protection in accordance with Section 5004.13 shall be provided for portable tanks and cylinders located outdoors ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use
6004.3 Highly Toxic and Toxic Materials, Outdoor Storage and Use
Weather protection in accordance with Section 5004.13 shall be provided for portable tanks and cylinders located outdoors ...