// CODE SNIPPET
5504.3.1.2 Outdoor Storage of Portable Containers
JUMP TO FULL CODE CHAPTER
Outdoor storage of portable containers shall comply with Section 5503 and Sections 5504.3.1.2.1 through 5504.3.1.2.3.
Portable containers in outdoor storage shall be separated from exposure hazards in accordance with Table 5504.3.1.2.1.
SEPARATION OF PORTABLE CONTAINERS FROM EXPOSURE HAZARDS
EXPOSURE | MINIMUM DISTANCE (feet) |
Building exits | 10 |
Wall openings | 1 |
Air intakes | 10 |
Lot lines | 5 |
Combustible materials such as paper, leaves, weeds, dry grass or debris | 15 |
Other hazardous materials | In accordance with Chapter 50 |
For SI: 1 foot = 304.8 mm.
The surface of the area on which stationary containers are placed, including the surface of the area located below the point where connections are made for the purpose of filling such containers, shall be compatible with the fluid in the container.
The area surrounding portable containers shall be provided with a means to prevent accidental discharge of fluids from endangering adjacent containers, buildings, equipment or adjoining property.
Exception: These provisions shall not apply where it is determined by the fire code official that the container does not constitute a hazard.
Related Code Sections
5504.3.1.2 Cryogenic Fluids, Outdoor Storage of Portable Containers
Outdoor storage of portable containers shall comply with Section 5503 and Sections 5504.3.1.2.1 through 5504.3.1.2.3 ...
Fire Code 2021 of Colorado > 55 Cryogenic Fluids > 5504 Storage > 5504.3 Outdoor Storage > 5504.3.1 Separation From Hazardous Conditions > 5504.3.1.2 Outdoor Storage of Portable Containers
5504.3.1.2 Cryogenic Fluids, Outdoor Storage of Portable Containers
Outdoor storage of portable containers shall comply with Section 5503 and Sections 5504.3.1.2.1 through 5504.3.1.2.3 ...
Fire Code 2018 of Colorado > 55 Cryogenic Fluids > 5504 Storage > 5504.3 Outdoor Storage > 5504.3.1 Separation From Hazardous Conditions > 5504.3.1.2 Outdoor Storage of Portable Containers
5504.3.1.2.3 Cryogenic Fluids, Drainage
The area surrounding portable containers shall be provided with a means to prevent accidental discharge of fluids from endangering adjacent ...
Fire Code 2018 of Colorado > 55 Cryogenic Fluids > 5504 Storage > 5504.3 Outdoor Storage > 5504.3.1 Separation From Hazardous Conditions > 5504.3.1.2 Outdoor Storage of Portable Containers > 5504.3.1.2.3 Drainage
5704.4.3 Flammable and Combustible Liquids, Spill Control and Secondary Containment
Storage areas shall be provided with spill control and secondary containment in accordance with Section 5703.4. Exception: Containers stored ...
Fire Code 2021 of Colorado > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.4 Outdoor Storage of Containers and Portable Tanks > 5704.4.3 Spill Control and Secondary Containment
5704.4.3 Flammable and Combustible Liquids, Spill Control and Secondary Containment
Storage areas shall be provided with spill control and secondary containment in accordance with Section 5703.4. Exception: Containers stored ...
Fire Code 2018 of Colorado > 57 Flammable and Combustible Liquids > 5704 Storage > 5704.4 Outdoor Storage of Containers and Portable Tanks > 5704.4.3 Spill Control and Secondary Containment