3404.4 Outdoor Storage of Containers
JUMP TO FULL CODE CHAPTER
Outdoor storage areas for portable containers of flammable and combustible liquids shall be designed, installed, operated and maintained in compliance with the requirements of FC 3403, and 3404.4.1 through 3404.4.8.
Outdoor portable container storage areas shall be designed and constructed in accordance with approved design and installation documents.
Outdoor portable container storage areas shall be designed, installed, operated and maintained in accordance with FC Table 3404.4.2 and in compliance with the requirements of FC 3404.4.2.1 through 3404.4.2.4.
FC TABLE 3404.4.2 OUTDOOR LIQUID STORAGE IN CONTAINERS
FC TABLE 3404.4.2 OUTDOOR LIQUID STORAGE IN CONTAINERS
CLASS OF LIQUID | CONTAINER STORAGE— MAXIMUM PER PILE | MINIMUM DISTANCE BETWEEN PILES OR RACKS (feet) | MINIMUM DISTANCE TO LOT LINEd (feet) | MINIMUM DISTANCE TO PUBLIC STREET OR PRIVATE ROADd (feet) | |
Quantitya, b (gallons) | Height (feet) | ||||
IA IB IC II III | 1,100 2,200 4,400 8,800 22,000 | 10 12 12 12 18 | 5 5 5 5 5 | 50 50 50 25 10 | 10 10 10 5 5 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 L. |
a. For mixed class storage, see FC3404.4.2. |
b. For storage in racks, the quantity limits per pile do not apply, but the rack arrangement shall be limited to a maximum of 50 feet in length and two rows or 9 feet in depth. |
c. Reserved. |
d. When the total quantity stored does not exceed 50 percent of the maximum allowed per pile, the distances are allowed to be reduced 50 percent, but not less than 3 feet. |
Where two or more classes of liquids are stored in a single pile, the quantity in the pile shall not exceed the smallest of maximum quantities for the classes of material stored.
A maximum amount of 1,100 gallons (4163 L) of flammable and combustible liquids stored in portable containers may be stored adjacent to a building located on the same premises and under the same ownership, provided that:
- The building does not exceed one story in height. Such building shall be of fire-resistance-rated construction with noncombustible exterior surfaces or noncombustible construction and shall be used principally for the storage of liquids; or
- The exterior building wall adjacent to the storage area shall have a fire-resistance rating of not less than 2 hours, having no openings to above grade areas within 10 feet (3048 mm) horizontally of such storage and no openings to below grade areas within 50 feet (15 240 mm) horizontally of such storage.
The quantity of liquids stored adjacent to a building protected in accordance with FC3404.4.2.4(2) may exceed 1,100 gallons (4163 L), provided that the maximum quantity per pile does not exceed 1,100 gallons (4163 L) and each pile is separated by a 10-foot-minimum (3048 mm) clear space along the common wall. Where the quantity stored exceeds 1,100 gallons (4163 L) adjacent to a building complying with FC3404.4.2.4(1), or the provisions of FC3404.4.2.4(1) cannot be met, a minimum distance in accordance with the column for distance to a lot line in FC Table 3404.4.2 shall be maintained between buildings and the nearest container.
Outdoor portable container storage areas shall be provided with spill control and secondary containment in accordance with FC3403.4.
Exception: Containers stored on approved containment pallets in accordance with FC2704.2.3 and containers stored in cabinets and lockers with integral spill containment.
Exception: Containers stored on approved containment pallets in accordance with FC2704.2.3 and containers stored in cabinets and lockers with integral spill containment.
Outdoor portable container storage areas shall be kept free from vegetation and other combustible waste as set forth in FC 3404.4.6.1 and 3404.4.6.2.
Rubbish and other combustible waste shall not be allowed to accumulate within 15 feet (4572 mm) of an outdoor portable container storage area.
The storage of empty containers previously used for the storage of flammable or combustible liquids shall be stored as required for filled containers. Containers when emptied shall have the covers or plugs immediately replaced in openings.
Related Code Sections
1305.9.13 Fuel-Oil Piping and Storage, Outdoor Fuel-Oil Piping in Existing Buildings
mm) from building openings and combustible construction.
Vertical outdoor fuel-oil piping shall be enclosed in a fully welded outer containment ...
NYC Mechanical Code 2022 > 13 Fuel-Oil Piping and Storage > 1305 Fuel-Oil System Installation > 1305.9 Supplemental Requirements for Piping From Transfer Pumps to Appliances or Storage Tanks Above Lowest Floor > 1305.9.13 Outdoor Fuel-Oil Piping in Existing Buildings
424.9 Special Detailed Requirements Based on Use and Occupancy, Storage Rooms
6 changes of air per hour and vents to the outdoors. Each entrance to the storage room shall be provided with a minimum 1 1 / 2 -hour rated self ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 424 Nonproduction Chemical Laboratories > 424.9 Storage Rooms
427.9 Special Detailed Requirements Based on Use and Occupancy, Storage Rooms
at least 6 changes of air per hour and vents to the outdoors.
Each entrance to the storage room shall be provided with a minimum 1 1 / 2 -hour rated self ...
NYC Building Code 2022 > 4 Special Detailed Requirements Based on Use and Occupancy > 427 Nonproduction Chemical Laboratories > 427.9 Storage Rooms
419.9 Special Detailed Requirements Based on Use and Occupancy, Storage Rooms
be provided with a sill at the doorway, except that no sill shall be required in storage rooms containing only flammable gases. 7. Storage ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 419 Non-Production Chemical Laboratories > 419.9 Storage Rooms
§28-502.2 Miscellaneous Provisions, Registration of Outdoor Advertising Companies
and storage of an illegal sign or sign structure under the control of such outdoor advertising company; and All fines or civil penalties imposed ...
NYC General Admin. Provisions 2014 > 5 Miscellaneous Provisions > 502 Outdoor Advertising Companies > §28-502.2 Registration of Outdoor Advertising Companies