6003.2 Outdoor Storage and Use
JUMP TO FULL CODE CHAPTER
Outdoor storage and use of highly toxic and toxic materials shall comply with Sections 6003.2.1 through 6003.2.6.
The outdoor storage or use of highly toxic and toxic solids or liquids in amounts not exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(4) shall be in accordance with Sections 5001, 5003 and 6001.
The outdoor storage or use of highly toxic and toxic solids or liquids in amounts exceeding the maximum allowable quantity per control area set forth in Table 5003.1.1(4) shall be in accordance with Sections 6001 and 6003.2 and Chapter 50.
The general requirements applicable to the outdoor storage of highly toxic or toxic solids and liquids shall be in accordance with Sections 6003.2.3.1 and 6003.2.3.2.
Outdoor storage or use of highly toxic or toxic solids and liquids shall not be located within 20 feet (6096 mm) of lot lines, public streets, public alleys, public ways, exit discharges or exterior wall openings. A 2-hour fire barrier without openings or penetrations extending not less than 30 inches (762 mm) above and to the sides of the storage is allowed in lieu of such distance. The wall shall either be an independent structure, or the exterior wall of the building adjacent to the storage area.
Exhaust scrubbers or other systems for processing vapors of highly toxic liquid shall be provided where a spill or accidental release of such liquids can be expected to release highly toxic vapors at normal temperature and pressure (NTP). Treatment systems and other processing systems shall be installed in accordance with the International Mechanical Code.
Outdoor storage piles of highly toxic and toxic solids and liquids shall be separated into piles not larger than 2,500 cubic feet (71 m3). Aisle widths between piles shall be not less than one-half the height of the pile or 10 feet (3048 mm), whichever is greater.
Where overhead weather protection is provided for outdoor storage or use of highly toxic liquids or solids, and the weather protection is attached to a building, the storage or use area shall either be equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, or storage or use vessels shall be fire resistive. Weather protection shall be provided in accordance with Section 5004.13 for storage and Section 5005.3.9 for use.
Related Code Sections
6003.2 Highly Toxic and Toxic Materials, Outdoor Storage and Use
Outdoor storage and use of highly toxic and toxic materials shall comply with Sections 6003.2.1 through 6003.2.6 ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6003 Highly Toxic and Toxic Solids and Liquids > 6003.2 Outdoor Storage and Use
6003.2 Highly Toxic and Toxic Materials, Outdoor Storage and Use
Outdoor storage and use of highly toxic and toxic materials shall comply with Sections 6003.2.1 through 6003.2.6 ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6003 Highly Toxic and Toxic Solids and Liquids > 6003.2 Outdoor Storage and Use
6004.3 Highly Toxic and Toxic Materials, Outdoor Storage and Use
The outdoor storage and use of highly toxic and toxic compressed gases shall be in accordance with Sections 6004.3.1 through 6004.3.4 ...
Fire Code 2018 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use
6004.3 Highly Toxic and Toxic Materials, Outdoor Storage and Use
The outdoor storage and use of highly toxic and toxic compressed gases shall be in accordance with Sections 6004.3.1 through 6004.3.4 ...
Fire Code 2021 of Colorado > 60 Highly Toxic and Toxic Materials > 6004 Highly Toxic and Toxic Compressed Gases > 6004.3 Outdoor Storage and Use
414.6 Special Detailed Requirements Based on Occupancy and Use, Outdoor Storage, Dispensing and Use
The outdoor storage, dispensing and use of hazardous materials shall be in accordance with the International Fire Code ...
Building Code 2021 of Colorado > 4 Special Detailed Requirements Based on Occupancy and Use > 414 Hazardous Materials > 414.6 Outdoor Storage, Dispensing and Use