// CODE SNIPPET
550.20 Outdoor Outlets, Luminaires, Air-Cooling Equipment, and So Forth
Go To Full Code Chapter
(A) Listed for Outdoor Use
Outdoor luminaires and equipment shall be listed for wet locations or outdoor use. Outdoor receptacles shall comply with 406.9. Where located on the underside of the home or located under roof extensions or similarly protected locations, outdoor luminaires and equipment shall be listed for use in damp locations.
(B) Outside Heating Equipment, Air-Conditioning Equipment, or Both
A mobile home provided with a branch circuit designed to energize outside heating equipment, air-conditioning equipment, or both, located outside the mobile home, other than room air conditioners, shall have such branch-circuit conductors terminate in a listed outlet box, or disconnecting means, located on the outside of the mobile home. A label shall be permanently affixed adjacent to the outlet box and shall contain the following information:
THIS CONNECTION IS FOR HEATING AND/OR AIR-CONDITIONING EQUIPMENT. THE BRANCH CIRCUIT IS RATED AT NOT MORE THAN___AMPERES, AT___VOLTS, 60 HERTZ,___CONDUCTOR AMPACITY. A DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT OF THE EQUIPMENT.
The correct voltage and ampere rating shall be given. The tag shall be not less than 0.51 mm (0.020 in.) thick etched brass, stainless steel, anodized or alclad aluminum, or equivalent. The tag shall not be less than 75 mm by 45 mm (3 in. by 13/4 in.) minimum size.
Related Code Sections
550.20 Special Occupancies, Outdoor Outlets, Luminaires, Air-Cooling Equipment, and So Forth
Outdoor luminaires and equipment shall be listed for wet locations or outdoor use. Outdoor receptacles shall comply with 406.9. Where located ...
(C) Special Occupancies, Outdoor Outlets, Luminaires, Air-Cooling Equipment, and So On
Outdoor luminaires and other equipment shall be listed for outdoor use or wet locations ...
(C) Special Occupancies, Outdoor Outlets, Luminaires, Air-Cooling Equipment, and So On
Outdoor luminaires and other equipment shall be listed for outdoor use ...
552.54 Special Occupancies, Luminaires
Outdoor luminaires and other equipment shall be listed for outdoor use or wet locations ...
(B) General, Cooling
Electrical equipment that depends on the natural circulation of air and convection principles for cooling of exposed surfaces shall be installed so ...