404.2 Outdoor Ornamental Fountains and Water Features
JUMP TO FULL CODE CHAPTER
Where available and approved for use by the authority having jurisdiction, alternate nonpotable onsite water sources complying with Chapter 7 shall be used for outdoor ornamental fountains and other water features constructed or installed on a building site. Where the fountain or water feature is the primary user of the building site's nonpotable water source, a potable makeup water connection is prohibited.
Exception: Outdoor ornamental fountains and water features are allowed to use potable water provided water is recirculated and there is not an automatic refill valve connection to a source of potable water, and provided that either:
- The catch basin or reservoir is no greater than 100 gallons (379 L); or
- Less than 20 square feet (1.86 m2) of water surface area is exposed.
The treatment required to maintain appropriate water quality shall comply with the authority having jurisdiction.
Outdoor ornamental fountains and water features shall be equipped to recirculate and reuse the supplied water.
Signage in accordance with Chapter 7 shall be posted at each outdoor ornamental fountain and water feature where nonpotable water is used.
Related Code Sections
404.2 Site Development and Land Use, Outdoor Ornamental Fountains and Water Features
be used for outdoor ornamental fountains and other water features constructed or installed on a building site. Where the fountain or water feature ...
Green Construction Code 2012 of Maryland > 4 Site Development and Land Use > 404 Landscape Irrigation and Outdoor Fountains > 404.2 Outdoor Ornamental Fountains and Water Features
423.1 Fixtures, Faucets and Fixture Fittings, Water Connections
Baptisteries, ornamental and lily pools, aquariums, ornamental fountain basins, swimming pools, and similar constructions, where provided with water ...
Plumbing Code 2018 of Maryland > 4 Fixtures, Faucets and Fixture Fittings > 423 Specialty Plumbing Fixtures > 423.1 Water Connections
Section 410 Fixtures, Faucets and Fixture Fittings, Drinking Fountains
Drinking fountains shall conform to ASME A112.19.1/CSA B45.2 or ASME A112.19.2/CSA B45.1 and water coolers shall conform to ASHRAE 18. Drinking ...