(B) Outdoor Installations
JUMP TO FULL CODE CHAPTER
Less-flammable liquid-filled transformers shall be permitted to be installed outdoors, attached to, adjacent to, or on the roof of buildings, if installed in accordance with (1) or (2).
- For Type I and Type II buildings, the installation shall comply with all the restrictions provided for in the listing of the liquid. Informational Note No. 1: Installations adjacent to combustible material, fire escapes, or door and window openings can require additional safeguards such as those listed in 450.27.Informational Note No. 2: Such restrictions can include, but are not limited to: maximum pressure of the tank, use of a pressure relief valve, appropriate fuse types, and proper sizing of overcurrent protection.
- In accordance with 450.27.
Informational Note No. 1: As used in this section, Type I and Type II buildings refers to Type I and Type II building construction as defined in NFPA 220—2018, Standard on Types of Building Construction. Combustible materials refers to those materials not classified as noncombustible or limited-combustible as defined in NFPA 220—2018, Standard on Types of Building Construction.
Informational Note No. 2: See definition of Listed in Article 100.
Related Code Sections
(C) General, Outdoor Installations
Outdoor electrical installations that are open to unqualified persons shall comply with Parts I, II, and III of Article 225 ...
National Electrical Code 2020 of Minnesota > 1 General > 110 Requirements for Electrical Installations > 110.31 Enclosure for Electrical Installations > (C) Outdoor Installations
1205.8 Energy Systems, Outdoor Installation
Stationary fuel cell power systems located outdoors shall be separated by not less than 5 feet (1524 mm) from the following: Lot lines. Public ...
2020 Minnesota State Fire Code > 12 Energy Systems > 1205 Stationary Fuel Cell Power Systems > 1205.8 Outdoor Installation
1206.2.8.7 Energy Systems, Outdoor Installations
requirements of Section 1206.2. Installations in outdoor enclosures or containers that can be occupied for servicing, testing, maintenance and other ...
2020 Minnesota State Fire Code > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.8 Location and Construction > 1206.2.8.7 Outdoor Installations
413.4.2 Gas Piping Installations, Outdoor Installation
Residential fueling appliance s located outdoors shall be installed on a firm, noncombustible base ...
Minnesota Fuel Gas Code 2015 > 4 Gas Piping Installations > 413 (IFGC) Compressed Natural Gas Motor Vehicle Fuel-Dispensing Facilities > 413.4 Residential Fueling Appliance Installation > 413.4.2 Outdoor Installation
(B) Equipment for General Use, Outdoor Installations
Less-flammable liquid-filled transformers shall be permitted to be installed outdoors, attached to, adjacent to, or on the roof of buildings ...
National Electrical Code 2020 of Minnesota > 4 Equipment for General Use > 450 Transformers and Transformer Vaults (Including Secondary Ties) > 450.23 Less-Flammable Liquid-Insulated Transformers > (B) Outdoor Installations