Stationary fuel cell power systems located outdoors shall be separated by not less than 5 feet (1524 mm) from the following:
- Lot lines.
- Public ways.
- Buildings.
- Stored combustible materials.
- Hazardous materials.
- High-piled stock.
- Any portion of a designated means of egress system.
- Other exposure hazards.
Related Code Sections
(C) General, Outdoor Installations
Outdoor electrical installations that are open to unqualified persons shall comply with Parts I, II, and III of Article 225 ...
National Electrical Code 2020 of Colorado > 1 General > 110 Requirements for Electrical Installations > 110.31 Enclosure for Electrical Installations > (C) Outdoor Installations
1205.8 Energy Systems, Outdoor Installation
Stationary fuel cell power systems located outdoors shall be separated by not less than 5 feet (1524 mm) from the following: Lot lines. Public ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1205 Stationary Fuel Cell Power Systems > 1205.8 Outdoor Installation
1206.2.8.7 Energy Systems, Outdoor Installations
requirements of Section 1206.2. Installations in outdoor enclosures or containers that can be occupied for servicing, testing, maintenance and other ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.8 Location and Construction > 1206.2.8.7 Outdoor Installations
1206.8 Energy Systems, Outdoor Installation
Stationary fuel cell power systems located outdoors shall be separated by not less than 5 feet (1524 mm) from the following: Lot lines. Public ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1206 Stationary Fuel Cell Power Systems > 1206.8 Outdoor Installation
1207.8 Energy Systems, Outdoor Installations
Outdoor installations shall be in accordance with Sections 1207.8.1 through 1207.8.3. Exterior wall installations for individual ESS ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1207 Electrical Energy Storage Systems (ESS) > 1207.8 Outdoor Installations