• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

5005.3 Outdoor Dispensing and Use

Fire Code 2018 of Colorado > 50 Hazardous Materials—General Provisions > 5005 Use, Dispensing and Handling > 5005.3 Outdoor Dispensing and Use
JUMP TO FULL CODE CHAPTER
Dispensing and use of hazardous materials outdoors shall be in accordance with Sections 5005.3.1 through 5005.3.9.

5005.3.1 Quantities Exceeding the Maximum Allowable Quantity Per Control Area

Outdoor dispensing or use of hazardous materials, in either closed or open containers or systems, in amounts exceeding the maximum allowable quantity per control area indicated in Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with Sections 5001, 5003, 5005.1 and 5005.3.

5005.3.2 Quantities Not Exceeding the Maximum Allowable Quantity Per Control Area

Outdoor dispensing or use of hazardous materials, in either closed or open containers or systems, in amounts not exceeding the maximum allowable quantity per control area indicated in Tables 5003.1.1(3) and 5003.1.1(4) shall be in accordance with Sections 5001 and 5003.

5005.3.3 Location

Outdoor dispensing and use areas for hazardous materials shall be located as required for outdoor storage in accordance with Section 5004.

5005.3.4 Spill Control for Hazardous Material Liquids in Open Systems

Outdoor areas where hazardous material liquids are dispensed in vessels exceeding a 1.3-gallon (5 L) capacity or used in open systems exceeding a 5.3-gallon (20 L) capacity shall be provided with spill control in accordance with Section 5004.2.1.

5005.3.5 Secondary Containment for Hazardous Material Liquids in Open Systems

Where required by Table 5005.2.1.4, outdoor areas where hazardous material liquids are dispensed or used in open systems shall be provided with secondary containment in accordance with Section 5004.2.2 where the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following:
  1. Individual vessel or system: greater than 1.3 gallons (5 L).
  2. Multiple vessels or systems: greater than 5.3 gallons (20 L).

5005.3.6 Spill Control for Hazardous Material Liquids in Closed Systems

Outdoor areas where hazardous material liquids are used in closed systems exceeding 55 gallons (208 L) shall be provided with spill control in accordance with Section 5004.2.1.

5005.3.7 Secondary Containment for Hazardous Material Liquids in Closed Systems

Where required by Table 5005.2.1.4, outdoor areas where hazardous material liquids are dispensed or used in closed systems shall be provided with secondary containment in accordance with Section 5004.2.2 where the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following:
  1. Individual vessel or system: greater than 55 gallons (208 L).
  2. Multiple vessels or systems: greater than 1,000 gallons (3785 L).

5005.3.8 Clearance From Combustibles

The area surrounding an outdoor dispensing or use area shall be kept clear of combustible materials and vegetation for a minimum distance of 30 feet (9144 mm).

5005.3.9 Weather Protection

Where overhead noncombustible construction is provided for sheltering outdoor hazardous material use areas, such use shall not be considered indoor use where the area is constructed in accordance with the requirements for weather protection as required in the International Building Code.
Exception: Use of explosive materials shall be considered as indoor use.

Related Code Sections


5005.3 Hazardous Materials—General Provisions, Outdoor Dispensing and Use
Dispensing and use of hazardous materials outdoors shall be in accordance with Sections 5005.3.1 through 5005.3.9 ...
Fire Code 2021 of Colorado > 50 Hazardous Materials—General Provisions > 5005 Use, Dispensing and Handling > 5005.3 Outdoor Dispensing and Use
5005.3 Hazardous Materials—General Provisions, Outdoor Dispensing and Use
Dispensing and use of hazardous materials outdoors shall be in accordance with Sections 5005.3.1 through 5005.3.9 ...
Fire Code 2018 of Colorado > 50 Hazardous Materials—General Provisions > 5005 Use, Dispensing and Handling > 5005.3 Outdoor Dispensing and Use
414.6 Special Detailed Requirements Based on Occupancy and Use, Outdoor Storage, Dispensing and Use
The outdoor storage, dispensing and use of hazardous materials shall be in accordance with the International Fire Code ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 4 Special Detailed Requirements Based on Occupancy and Use > 414 Hazardous Materials > 414.6 Outdoor Storage, Dispensing and Use
414.6 Special Detailed Requirements Based on Use and Occupancy, Outdoor Storage, Dispensing and Use
The outdoor storage, dispensing and use of hazardous materials shall be in accordance with the International Fire Code ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 4 Special Detailed Requirements Based on Use and Occupancy > 414 Hazardous Materials > 414.6 Outdoor Storage, Dispensing and Use
414.6 Special Detailed Requirements Based on Occupancy and Use, Outdoor Storage, Dispensing and Use
The outdoor storage, dispensing and use of hazardous materials shall be in accordance with the International Fire Code ...
Building Code 2021 of Colorado > 4 Special Detailed Requirements Based on Occupancy and Use > 414 Hazardous Materials > 414.6 Outdoor Storage, Dispensing and Use
Help Contact Us Privacy Terms
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING