403.2 Outdoor Air Required
JUMP TO FULL CODE CHAPTER
The minimum outdoor airflow rate shall be determined in accordance with Section 403.3.
Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding that obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
The outdoor air required by Section 403.3 shall not be recirculated. Air in excess of that required by Section 403.3 shall not be prohibited from being recirculated as a component of supply air to building spaces, except that:
- Ventilation air shall not be recirculated from one dwelling to another or to dissimilar occupancies.
- Supply air to a swimming pool and associated deck areas shall not be recirculated unless such air is dehumidified to maintain the relative humidity of the area at 60 percent or less. Air from this area shall not be recirculated to other spaces where more than 10 percent of the resulting supply airstream consists of air recirculated from these spaces.
- Where mechanical exhaust is required by Note b in Table 403.3.1.1, recirculation of air from such spaces shall be prohibited. Recirculation of air that is contained completely within such spaces shall not be prohibited. Where recirculation of air is prohibited, all air supplied to such spaces shall be exhausted, including any air in excess of that required by Table 403.3.1.1.
- Where mechanical exhaust is required by Note g in Table 403.3.1.1, mechanical exhaust is required and recirculation from such spaces is prohibited where more than 10 percent of the resulting supply air-stream consists of air recirculated from these spaces. Recirculation of air that is contained completely within such spaces shall not be prohibited.
Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air transferred from occupiable spaces is not prohibited from serving as makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1. The required outdoor airflow rates specified in Table 403.3.1.1 shall be introduced directly into such spaces or into the occupied spaces from which air is transferred or a combination of both.
Related Code Sections
403.2 Ventilation, Outdoor Air Required
of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance ...
Mechanical Code 2018 of Maryland > 4 Ventilation > 403 Mechanical Ventilation > 403.2 Outdoor Air Required
Section 405 Ventilation, Systems Control
Air-conditioning systems that supply required ventilation air shall be provided with controls designed to automatically maintain the required outdoor ...
403.3.1.1.1 Ventilation, Zone Outdoor Airflow
The minimum outdoor airflow required to be supplied to each zone shall be determined as a function of occupancy classification and space air ...
Mechanical Code 2018 of Maryland > 4 Ventilation > 403 Mechanical Ventilation > 403.3 Outdoor Air and Local Exhaust Airflow Rates > 403.3.1 Other Buildings Intended to Be Occupied > 403.3.1.1 Outdoor Airflow Rate > 403.3.1.1.1 Zone Outdoor Airflow