// CODE SNIPPET
403.5.4 Outdoor Air Intake
JUMP TO FULL CODE CHAPTER
The design outdoor air intake flow (Vot) shall be determined in accordance with Equation 403.5.4. [ASHRAE 62.1:6.2.5.4]
(Equation 403.5.4)
Vot = Vou/Ev
Related Code Sections
403.5.4 Ventilation Air, Outdoor Air Intake
The design outdoor air intake flow ( V ot ) shall be determined in accordance with Equation 403.5.4. [ASHRAE 62.1:6.2.5.4] (Equation 403.5.4) V ...
Uniform Mechanical Code 2018 of Nevada > 4 Ventilation Air > 403.0 Ventilation Rates > 403.5 Multiple-Zone Recirculating Systems > 403.5.4 Outdoor Air Intake
6.3.1 Systems and Equipment, Outdoor Air Intakes
Outdoor air intakes for AHUs shall be located a minimum of 25 ft (8 m) from cooling towers and all exhaust and vent discharges. Outdoor air intakes ...
Guidelines for Design and Construction of Outpatient Facilities 2018 of Nevada > 6 Systems and Equipment > 6.3 Outdoor Air Intakes and Exhaust Discharges > 6.3.1 Outdoor Air Intakes
6.3.1 Systems and Equipment, Outdoor Air Intakes
Outdoor air intakes for AHUs shall be located a minimum of 25 ft (8 m) from cooling towers and all exhaust and vent discharges. Outdoor air intakes ...
Guidelines for Design and Construction of Hospitals 2018 of Nevada > 6 Systems and Equipment > 6.3 Outdoor Air Intakes and Exhaust Discharges > 6.3.1 Outdoor Air Intakes
402.4 Ventilation Air, Outdoor Air Intake Protection
Required outdoor-air intakes shall be covered with a screen having not less than 1 / 4 of an inch (6.4 mm) openings, and shall have not more than ...
Uniform Mechanical Code 2018 of Nevada > 4 Ventilation Air > 402.0 Ventilation Air > 402.4 Outdoor Air Intake Protection
C402.4.5.2 [CE] Commercial Energy Efficiency, Outdoor Air Intakes and Exhausts
intakes and exhaust and relief dampers in buildings of any height located in Climate Zones 1, 2 and 3.
Where the design outdoor air intake ...
Energy Conservation Code 2012 of Nevada > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.4 Air Leakage (Mandatory) > C402.4.5 Air Intakes, Exhaust Openings, Stairways and Shafts > C402.4.5.2 Outdoor Air Intakes and Exhausts