403.3.2.2 Outdoor Air for Other Spaces
JUMP TO FULL CODE CHAPTER
Corridors and other common areas within the conditioned space shall be provided with outdoor air at a rate of not less than 0.06 cfm per square foot of floor area.
Related Code Sections
403.3.2.2 Ventilation, Outdoor Air for Other Spaces
Corridors and other common areas within the conditioned space shall be provided with outdoor air at a rate of not less than 0.06 cfm per square foot ...
Mechanical Code 2018 of Maryland > 4 Ventilation > 403 Mechanical Ventilation > 403.3 Outdoor Air and Local Exhaust Airflow Rates > 403.3.2 Group R-2, R-3 and R-4 Occupancies, Three Stories and Less > 403.3.2.2 Outdoor Air for Other Spaces
R1006.2 Chimneys and Fireplaces, Exterior Air Intake
ventilated with outdoor air such as nonmechanically ventilated crawl or attic spaces. The exterior air intake shall not be located within the garage ...
Residential Code 2015 of Maryland > 10 Chimneys and Fireplaces > R1006 Exterior Air Supply > R1006.2 Exterior Air Intake
R1006.2 Chimneys and Fireplaces, Exterior Air Intake
ventilated with outdoor air such as nonmechanically ventilated crawl or attic spaces. The exterior air intake shall not be located within the garage ...
Residential Code 2018 of Maryland > 10 Chimneys and Fireplaces > R1006 Exterior Air Supply > R1006.2 Exterior Air Intake
606.7 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Kitchen Exhaust Systems
the purposes of this section, available transfer air is considered to be that portion of outdoor ventilation air not required to satisfy other exhaust ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 606 Building Mechanical Systems > 606.7 Kitchen Exhaust Systems