// CODE SNIPPET
1228.13.1.2 Outdoor Activity Area
JUMP TO FULL CODE CHAPTER
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements:
- Fences and walls shall be designed to:
- Be installed with tamper-resistant hardware.
- Have a minimum height of 10 feet (3048 mm) above the outdoor area elevation.
- Be anchored and constructed to withstand the body force of a 350-pound (158-kg) person.
- If provided, gates or doors in the fence or wall
shall:
- Lights shall not be accessible to patients. Lighting in the outdoor activity area shall not be pole mounted.
- If provided, security cameras shall not be accessible to patients and cameras shall view the entire outdoor activity area.
- If provided, furniture shall be secured from movement. Furniture shall not be placed in locations where it can be used to climb the fence or wall.
Related Code Sections
1228.13.1.2 Interior Environment, Outdoor Activity Area
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements:
Fences and walls shall be designed ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1228 Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space > 1228.13.1 Patient Care Areas > 1228.13.1.2 Outdoor Activity Area
1228.13.1.2 Interior Environment, Outdoor Activity Area
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements:
Fences and walls shall be designed ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space > 1228.13.1 Patient Care Areas > 1228.13.1.2 Outdoor Activity Area
1228.13.1 Interior Environment, Patient Care Areas
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements:
Fences ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space > 1228.13.1 Patient Care Areas
1228.13 Interior Environment, Psychiatric Rehabilitation Activities Service Space
An outdoor activity
area shall be provided. Outdoor areas shall meet the
following requirements ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1228 [OSHPD 5] Acute Psychiatric Hospitals > 1228.13 Psychiatric Rehabilitation Activities Service Space
1230.1.11 Interior Environment, Physical Activity and Recreation Areas
Indoor / outdoor physical activity and recreation areas shall be designed as follows: 1. Facility capacity Minimum indoor outdoor ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1230 [BSCC] Minimum Standards for Juvenile Facilities > 1230.1 Design Criteria for Required Spaces > 1230.1.11 Physical Activity and Recreation Areas